Yaskawa AC Drive P1000 Bypass Technical Manual User Manual
Page 322

Register No.
Contents
0099H
Low Word of Accumulated Operation Time Monitor, 1 h units (U4-01)
009AH
High Word of Cooling Fan Operation Time Monitor (U4-03)
009BH
Low Word of Cooling Fan Operation Time Monitor (U4-03)
009CH to 00AAH
Reserved
00ABH
Drive Rated Current
<2>
00ACH
Motor Speed (U1-05)
Note: Not available in
P1000.
r/min units
<4>
00ADH
0.01% units
00AEH to 00B4H
Reserved
00B5H
Frequency Reference After
Soft-starter (U1-16)
r/min units
<4>
00B6H
0.01% units
00B7H
Frequency Reference
r/min
<4>
00B8H
0.01% units
00B9H to 00BEH
Reserved
00BFH
Lists the last two digits of operation error code oPEoo.
00C0H
Fault Contents 3
bit 1
Undervoltage (Uv1)
bit 2
Control Power Supply Undervoltage (Uv2)
bit 3
Soft Charge Circuit Fault (Uv3)
bit 4
Reserved
bit 5
Ground Fault (GF)
bit 6
Overcurrent (oC)
bit 7
Overvoltage (ov)
bit 8
Heatsink Overheat (oH)
bit 9
Heatsink Overheat (oH1)
bit A
Motor Overload (oL1)
bit B
Drive Overload (oL2)
bit C
Overtorque Detection 1 (oL3)
bit D to F
Reserved
00C1H
Fault Contents 4
bit 0
External Fault at input terminal S3 (EF3)
bit 1
External Fault at input terminal S4 (EF4)
bit 2
External Fault at input terminal S5 (EF5)
bit 3
External Fault at input terminal S6 (EF6)
bit 4
External Fault at input terminal S7 (EF7)
bit 5
Reserved
bit 6
Cooling Fan Error (FAn)
bit 7 to 9
Reserved
bit A
Input Phase Loss (PF)
bit B
Output Phase Loss (LF)
bit C
Motor Overheat (PTC input) (oH3)
bit D
Digital Operator Connection Fault (oPr)
bit E
EEPROM Write Error (Err)
bit F
Motor Overheat Fault (PTC input) (oH4)
D.9 MEMOBUS/Modbus Data Table
322