5.12 U: Monitor Parameters
Monitor parameters let the user view various aspects of drive performance using the HOA keypad display. Some monitors
can be output from terminals FM and AM by assigning the specific monitor parameter number (Uo-oo) to H4-01 and H4-04.
Refer to H4-01, H4-04: Multi-Function Analog Output Terminal FM, AM Monitor Selection on page 123
for details on
assigning functions to an analog output.
u
UB: Bypass Monitors
These monitors display various aspects of bypass control.
Refer to UB: Bypass Control Monitors on page 259
for a complete
list of UB-oo monitors and descriptions.
u
U1: Operation Status Monitors
Status monitors display drive status data such as output frequency and output current.
for a complete list of U1-oo monitors and descriptions.
u
U2: Fault Trace
Use these monitor parameters to view the status of various drive aspects when a fault occurs.
This information is helpful for determining the cause of a fault.
Refer to U2: Fault Trace on page 262
for a complete list of
U2-oo monitors and descriptions.
U2-oo monitors are not reset when the drive is initialized.
Note:
Fault histories are not kept when CPF00, CPF01, CPF06, CPF24, oFA00, oFb00, oFC00, Uv1, Uv2, or Uv3 occur.
u
U3: Fault History
These parameters display faults that have occurred during operation as well as the drive operation time when those faults
occurred.
Refer to U3: Fault History on page 263
for a complete list of U3-oo monitors and descriptions.
U3-oo monitors are not reset when the drive is initialized.
Note:
Fault histories are not kept when CPF00, CPF01, CPF06, CPF24, oFA00, oFb00, oFC00, Uv1, Uv2, or Uv3 occur.
u
U4: Maintenance Monitors
Maintenance monitors show:
• Runtime data of the drive and cooling fans and number of Run commands issued
• Maintenance data and replacement information for various drive components
• kWh data
• Highest peak current that has occurred and output frequency at the time the peak current occurred
• Motor overload status information
• Detailed information about the present Run command and frequency reference source selection
Refer to U4: Maintenance Monitors on page 264
for a complete list of U4-oo monitors and descriptions.
u
U5: PID Monitors
These monitors display various aspects of PID control.
Refer to PID Block Diagram on page 93
for details on how these
monitors display PID data.
Refer to U5: PID Monitors on page 266
for a complete list of U5-oo monitors and descriptions.