Yaskawa AC Drive P1000 Bypass Technical Manual User Manual
Page 145

Sequence Timers 2 to 4
These timers operate identically to Sequence Timer 1. Parameters S2-06 to S2-20 configure Sequence Timers 2 to 4.
Priority
If multiple sequence timers overlap, the timer with the lowest number has priority.
Sequence Timer 1 = highest priority
Sequence Timer 4 = lowest priority
n
S2-01/S2-06/S2-11/S2-16: Sequence Timers 1 to 4 Start Time
Sets the start times for timers 1 to 4. The values must be set less than or equal to S2-02/S2-07/S2-12/S2-17.
No.
Name
Setting Range
Default
S2-01
Sequence Timer 1 Start Time
00:00 to 24:00
00:00
S2-06
Sequence Timer 2 Start Time
00:00 to 24:00
00:00
S2-11
Sequence Timer 3 Start Time
00:00 to 24:00
00:00
S2-16
Sequence Timer 4 Start Time
00:00 to 24:00
00:00
n
S2-02/S2-07/S2-12/S2-17: Sequence Timers 1 to 4 Stop Time
Sets the stop times for timers 1 to 4. The values must be set greater than or equal to S2-01/S2-06/S2-11/S2-16.
No.
Name
Setting Range
Default
S2-02
Sequence Timer 1 Stop Time
00:00 to 24:00
00:00
S2-07
Sequence Timer 2 Stop Time
00:00 to 24:00
00:00
S2-12
Sequence Timer 3 Stop Time
00:00 to 24:00
00:00
S2-17
Sequence Timer 4 Stop Time
00:00 to 24:00
00:00
n
S2-03/S2-08/S2-13/S2-18: Sequence Timers 1 to 4 Day Selection
Sets the days for which sequence timers 1 to 4 are active.
No.
Name
Setting Range
Default
S2-03
Sequence Timer 1 Day Selection
0 to 10
0
S2-08
Sequence Timer 2 Day Selection
0 to 10
0
S2-13
Sequence Timer 3 Day Selection
0 to 10
0
S2-18
Sequence Timer 4 Day Selection
0 to 10
0
Setting 0: Timer Disabled
Setting 1: Daily
Setting 2: Mon - Fri
Setting 3: Sat - Sun
Setting 4: Monday
Setting 5: Tuesday
Setting 6: Wednesday
Setting 7: Thursday
Setting 8: Friday
Setting 9: Saturday
Setting 10: Sunday
n
S2-04/S2-09/S2-14/S2-19: Sequence Timers 1/2/3/4 Selection
Sets the action that occurs when sequence timers 1 to 4 are active.
No.
Name
Setting Range
Default
S2-04
Sequence Timer 1 Selection
0 to 2
0
S2-09
Sequence Timer 2 Selection
0 to 2
0
S2-14
Sequence Timer 3 Selection
0 to 2
0
5.11 S: Special Parameters
YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual
145
5
Programming