beautypg.com

Control circuit terminal block functions, Input terminals – Yaskawa D1000 Series Power Regenerative Converter User Manual

Page 76

background image

3.9 Control Circuit Wiring

76

YASKAWA ELECTRIC TOEP C710656 07C YASKAWA Power Regenerative Converter - D1000 Instruction Manual

Control Circuit Terminal Block Functions

Parameters determine which functions apply to the multi-function digital inputs (S1 to S8), multi-function relay outputs
(M1, M2, M3, M4, M5, M6), and multi-function analog monitor outputs (FM, AM). The default setting is listed next to
each terminal name in

Table 3.8

.

NOTICE: Install an MC on the power supply side of the converter when the drive should not automatically restart after power loss. To

get the full performance life out of the electrolytic capacitors and circuit relays, refrain from switching the power supply off and on more

than once every 30 minutes. Frequent use can damage the converter.

Input Terminals

Table 3.8

lists the input terminals on the converter. Text in parenthesis indicates the default setting for each multi-function

input.

Table 3.8 Control Circuit Input Terminals

<3> Set DIP switch S1 to select between a voltage or current input signal to terminal A2. The default setting is for current input. For

details, refer to

Terminal A2 Input Signal Selection on page 81

.

<4> Set DIP switch S2 to the ON position to enable the termination resistor in a MEMOBUS/Modbus network.

<5> Monitor outputs work with devices such as analog frequency meters, ammeters, voltmeters, and wattmeters. They are not intended

for use as a feedback-type signal.

Type

No.

Terminal Name (Function)

Function (Signal Level) Default

Setting

Page

Multi-Function
Digital Inputs

S1

Multi-function input 1 (RUN-SB)

• Photocoupler
• 24 Vdc, 8 mA
• Set the S3 jumper to select between

sinking, sourcing mode, and the power
supply. Refer to

Control I/O

Connections on page 81

.

186

S2

Multi-function input 2 (STOP)

S3

Multi-function input 3 (External fault)

S4

Multi-function input 4 (Fault reset)

S5

Multi-function input 5 (Reserved)

S6

Multi-function input 6 (Reserved)

S7

Multi-function input 7 (Reserved)

S8

Multi-function input 8 (External Baseblock)

SC

Multi-function input common

SP

Digital input power supply +24 Vdc

24 Vdc power supply for digital inputs,
150 mA max (only when not using digital
input option DI-A3)

NOTICE: Do not jumper or short

terminals SP and SN. Failure to

comply will damage the converter.

SN

Digital input power supply 0 V

Analog Inputs

+V

Analog reference input

10.5 Vdc (max allowable current 20 mA)

-V

Analog reference input

-10.5 Vdc (max allowable current 20 mA)

A1

Multi-function analog input 1 (Reserved)

-10 to 10 Vdc, 0 to 10 Vdc (input
impedance: 20 k

Ω)

188

A2

Multi-function analog input 2 (Reserved)

• -10 to 10 Vdc, 0 to 10 Vdc (input

impedance: 20 k

Ω)

• 4 to 20 mA, 0 to 20 mA (input

impedance: 250

Ω)

• Voltage or current input must be

selected by DIP switch S1 and H3-09.

189

A3

Multi-function analog input 3 (Reserved)

• -10 to 10 Vdc, 0 to 10 Vdc (input

impedance: 20 k

Ω)

• Use DIP switch S4 on the terminal

board to select between analog and PTC
input.

189

AC

Frequency reference common

0 V

E (G)

Ground for shielded lines and option cards

TOEP_C710656_07C_2_0.book 76 ページ 2015年1月9日 金曜日 午後6時23分