3.8 Harmonic Filter Module Wiring
YASKAWA ELECTRIC TOEP C710656 07C YASKAWA Power Regenerative Converter - D1000 Instruction Manual
69
El
ec
tr
ical
I
n
st
al
lat
ion
3
◆ Terminal Functions
Table 3.5 Terminal Functions
◆ Protecting Circuit Terminals
■
Insulation Caps or Sleeves
Use insulation caps or sleeves when wiring the module with crimp terminals. Take particular care to ensure that the wiring
does not touch nearby terminals or the surrounding case.
◆ Wire Gauges and Tightening Torque
Use the tables in this section to select the appropriate wires and crimp terminals.
Note: 1. Wire gauge recommendations based on continuous current ratings using 75
°C 600 Vac vinyl-sheathed wire assuming ambient
temperature within 40
°C.
2. Wire gauge recommendations for models 4A0270 to 4A0630 based on continuous current ratings using 105
°C 600 Vac vinyl-sheathed
wire assuming ambient temperature within 40
°C.
Consider the amount of voltage drop when selecting wire gauges. Increase the wire gauge when the voltage drop is
greater than 2% of motor rated voltage. Ensure the wire gauge is suitable for the terminal block. Use the following
formula to calculate the amount of voltage drop:
Line drop voltage (V) =
× wire resistance (Ω/km) × wire length (m) × current (A) × 10
-3
Terminal
Type
Function
Page
R/L1
Main circuit power supply inputs
These terminals are connected to the power supply.
S/L2
T/L3
r
Power supply voltage detection inputs
These terminals are to detect the power supply voltage order
and voltage levels.
t
X
Harmonic filter module outputs
These terminals connect to the input-side AC reactor.
–
Y
Z
For 200 V class: 100
Ω or less
For 400 V class: 10
Ω or less
Grounding terminal