B.2 Parameter Tables
184
YASKAWA ELECTRIC TOEP C710656 07C YASKAWA Power Regenerative Converter - D1000 Instruction Manual
◆ d: References
Reference parameters set the value of the DC bus voltage reference.
◆ F: Options
F parameters program the converter for communication options and to function with option cards.
C7-47
(112EH)
Adjustment Reactor
1
L1 Compensation
There is normally no need to change this parameter from
the default value.
Set this parameter to the value that is specified by the
manufacturer when using a filter such as the DC5.
Default:
Min.: 00.000
Max.: 65.000
C7-50
(113BH)
Operation Ready
ON Delay Time
Conv READY delay
Sets the delay time to turn on the Operation Ready signal
(H2- = 6).
Default: 0 ms
Min.: 0 ms
Max.: 500 ms
C7-51
(113CH)
Adjustment Reactor
2
L2 Compensation
There is normally no need to change this parameter from
the default value.
Set this parameter to the value that is specified by the
manufacturer when using a filter such as the DC5.
Default:
Min.: 00.000
Max.: 65.000
<1> This parameter is not available in model 4A0630.
<2> Default setting is dependent on parameter o2-04, Drive Model Selection.
No.
(Address
Hex)
Name
LCD Display
Description
Values
d8: DC Bus Voltage Reference
d8-01
(2B9H)
DC Bus Voltage
Reference
Vpn Volt Ref
Sets the DC bus voltage reference in volts.
Yaskawa recommends setting a value that is 1.5 times the
set value of the Power Supply Voltage (U1-54).
200 V Class
Default: 330 V
Range:300 V to
360 V
400 V Class
Default: 660 V
Range: 600 V to
730 V
No.
(Address
Hex)
Name
LCD Display
Description
Values
F4: Analog Monitor Card (AO-A3)
F4-01
(391H)
Terminal V1
Monitor Selection
AO Ch1 Select
Sets the monitor signal for output from terminal V1. Set
this parameter to the last three digits of the desired
U- monitor. Some U parameters are available only
in certain control modes.
Default: 0
Min.: 000
Max.: 408
F4-02
(392H)
Terminal V1
Monitor Gain
AO Ch1 Gain
Sets the gain for voltage output via terminal V1.
Default: 100.0%
Min.: -999.9%
Max.: 999.9%
F4-03
(393H)
Terminal V2
Monitor Selection
AO Ch2 Select
Sets the monitor signal for output from terminal V2. Set
this parameter to the last three digits of the desired
U- monitor. Some U parameters are available only
in certain control modes.
Default: 0
Min.: 000
Max.: 408
F4-04
(394H)
Terminal V2
Monitor Gain
AO Ch2 Gain
Sets the gain for voltage output via terminal V2.
Default: 50.0%
Min.: -999.9%
Max.: 999.9%
No.
(Address
Hex)
Name
LCD Display
Description
Values