Input-side ac reactor 1 – Yaskawa D1000 Series Power Regenerative Converter User Manual
Page 169

7.4 Standard Configuration Devices Wiring
YASKAWA ELECTRIC TOEP C710656 07C YASKAWA Power Regenerative Converter - D1000 Instruction Manual
169
St
an
d
ar
d
C
o
n
fi
g
u
rat
io
n De
vi
ce
s,
P
er
ip
h
er
al
Dev
ices
, a
nd Opt
ions
7
■
Input-side AC Reactor 1
Table 7.4 Wire Gauge and Torque Specifications
CIMR-D
Terminals
For Asia
For U.S.A.
For Europe and China
Screw
Size
Tightening
Torque
Nm
(lbin.)
Recomm.
Gauge
mm
2
Applicable
Gauge
mm
2
Recomm.
Gauge
AWG, kcmil
Applicable
Gauge
AWG, kcmil
Recomm.
Gauge
mm
2
Applicable
Gauge
mm
2
200 V Class
<1> Gauges listed here are for use in Japan.
<2> Gauges listed here are for use in the United States.
<3> Gauges listed here are for use in Europe and China.
2A0005
U, V, W
2
2 to 5.5
12
12 to 10
4
4 to 6
M4
1.0 to 1.3
(8.9 to 11.5)
X, Y, Z
2A0010
U, V, W
5.5
5.5 to 14
8
8 to 6
4
4 to 16
M5
2.0 to 2.5
(17.7 to 22.1)
X, Y, Z
2A0020
U, V, W
14
14 to 22
4
4
16
16 to 25
M6
4.0 to 4.9
(35.4 to 43.4)
X, Y, Z
2A0030
U, V, W
38
38
2
2 to 1
25
25 to 35
M8
8.9 to 10.7
(79.7 to 97.4)
X, Y, Z
2A0050
U, V, W
60
60
3
3 to 2/0
50
50 to 70
M8
8.9 to 10.7
(79.7 to 97.4)
X, Y, Z
2A0065
U, V, W
80
× 2P
80
3/0
× 2P
3/0
95
95
M12
31.4 to 39.2
(283 to 354)
X, Y, Z
2A0090
U, V, W
80
× 2P
80 to 100
3/0
× 2P
3/0 to 4/0
95
× 2P
95
M12
32 to 40
(283 to 354)
X, Y, Z
2A0130
U, V, W
100
× 2P
100 to 200
300
× 2P
300 to 400
95
× 2P
95 to 240
M12
32 to 40
(283 to 354)
X, Y, Z
400 V Class
4A0005
U, V, W
1.25
1.25 to 5.5
12
12 to 10
4
4 to 6
M4
1.0 to 1.3
(8.9 to 11.5)
X, Y, Z
4A0010
U, V, W
2
2 to 5.5
12
12 to 10
4
4 to 6
M4
1.0 to 1.3
(8.9 to 11.5)
X, Y, Z
4A0020
U, V, W
8
8
8
8
6
6 to 10
M6
4.0 to 4.9
(35.4 to 43.4)
X, Y, Z
4A0030
U, V, W
14
14
6
6
10
10 to 16
M8
8.9 to 10.7
(79.7 to 97.4)
X, Y, Z
4A0040
U, V, W
14
14 to 22
4
4
16
16 to 25
M8
8.9 to 10.7
(79.7 to 97.4)
X, Y, Z
4A0060
U, V, W
38
38
2
2 to 1
25
25 to 35
M8
8.9 to 10.7
(79.7 to 97.4)
X, Y, Z
4A0100
U, V, W
60
60
3
× 2P
3 to 2/0
50
50 to 70
M8
8.9 to 10.7
(79.7 to 97.4)
X, Y, Z
4A0130
U, V, W
80
× 2P
80
3/0
× 2P
3/0
95
95
M12
32 to 40
(283 to 354)
X, Y, Z
4A0185
U, V, W
80
× 2P
80 to 100
3/0
× 2P
3/0 to 4/0
95
× 2P
95
M12
32 to 40
(283 to 354)
X, Y, Z
4A0270
U, V, W
60
× 2P
60 to 150
300
× 2P
300
95
× 2P
95 to 150
M12
32 to 40
(283 to 354)
X, Y, Z
4A0370
U, V, W
100
× 2P
100 to 200
4/0
× 4P
4/0 to 300
150
× 2P
150 to 240
M12
32 to 40
(283 to 354)
X, Y, Z
4A0630
U, V, W
100
× 4P
100 to 200
4/0
× 8P
4/0 to 300
150
× 4P
150 to 240
M12
32 to 40
(283 to 354)
X, Y, Z
TOEP_C710656_07C_2_0.book 169 ページ 2015年1月9日 金曜日 午後6時23分