◆ C: Tuning
Tuning parameters set the voltage increase time, voltage decrease time, carrier frequency, and DC bus voltage control.
No.
(Address
Hex)
Name
LCD Display
Description
Values
C1: Voltage Increase and Decrease Times
C1-20
(265H)
Voltage Increase
Time
Vref Inc Ramp t
Sets the output voltage increase time in seconds.
Set the time to increase from 0% to 100%.
400 V Class: 800 V/C1-20 (V/s)
200 V Class: 400 V/C1-20 (V/s)
Default: 10.0 s
Min.: 0.0 s
Max.: 100.0 s
C1-21
(266H)
Voltage Decrease
Time
Vref Dec Ramp t
Sets the output voltage decrease time in seconds.
Set the time to decrease from 100% to 0%.
400 V Class: 800 V/C1-21 (V/s)
200 V Class: 400 V/C1-21 (V/s)
Default: 10.0 s
Min.: 0.0 s
Max.: 100.0 s
C6: Carrier Frequency
C6-03
(225H)
Carrier Frequency
Upper Limit
CarrierFreq Max
C6-03 is displayed on the operator, but cannot be set.
–
C7: DC Bus Voltage Control
C7-01
(253H)
DC Bus Voltage
Control (Avr)
Proportional Gain
AVR P Gain
Sets the proportional gain for DC bus voltage control
(Avr).
Default: 20.00
Min.: 1.00
Max.: 300.00
C7-02
(254H)
DC Bus Voltage
Control (Avr)
Integral Time
AVR I Time
Sets the integral time for DC bus voltage control (Avr).
Default: 0.500 s
Min.: 0.000 s
Max.: 10.000 s
C7-03
(255H)
DC Bus Voltage
Control (Avr)
Primary Delay Time
Constant
AVR Delay Time
Sets the primary delay time constant for DC bus voltage
control (Avr).
Default: 0.000 s
Min.: 0.000 s
Max.: 0.500 s
C7-12
(26EH)
Reactive Current
Reference Bias
Automatic
Calculation
Selection
React I Bias Sel
There is normally no need to change this parameter from
the default value. Sets whether to automatically calculate
the leading current compensation for the control process to
compensate the leading current in the reactive current
reference so that the leading current becomes 0.
0: Disabled
1: Enable (Automatically calculate the reactive current
reference bias.)
Default: 1
Range: 0, 1
C7-41
(1128H)
Gain for Active
Damping 2
Damp Gain 2
There is normally no need to change this parameter from
the default value.
Default: 0.000
Min.: 0.000
Max.: 10.000
C7-42
(1129H)
Gain for Automatic
Compensation of
Leading Current
Id Bias Gain
There is normally no need to change this parameter from
the default value.
It is used to make fine adjustments to the power factor.
Default: 100.0%
Min.: 0.0%
Max.: 1000.0%
C7-43
(112AH)
Input Voltage Offset
Adjustment
Vac Bias Adj Sel
There is normally no need to change this parameter from
the default value. This parameter is for factory setting.
If the setting is not correct, the converter may be damaged.
0: Standard
1: Start offset adjustment. (The parameter returns to 0 after
it is set.)
2: Offset adjustment not required. (The parameter returns
to 0 after it is set.)
Default: 0
Range: 0 to 2
C7-44
(112BH)
Gain for Active
Damping 3
Damping Gain 3
There is normally no need to change this parameter from
the default value.
Default: 0.00
Min.: 0.00
Max.: 1.00