Yaskawa D1000 Series Power Regenerative Converter User Manual
Page 223

C.9 MEMOBUS/Modbus Data Table
YASKAWA ELECTRIC TOEP C710656 07C YASKAWA Power Regenerative Converter - D1000 Instruction Manual
223
MEMO
BUS/Mod
bus
Co
mmunica
tion
s
C
00B0H
Option Code Connected to
CN5-A
Register contains ASCII code of the option card.
DO-A3 = 0002H
AI-A3 = 0003H
AO-A3 = 0004H
Communication Option: Register contains ASCII code of first and third digit of the option
card type number.
Example: Register value is 5343H for “SC” if an SI-C3 option card is installed.
00B1H
Reserved
00B2H
Option Code Connected to CN5-B
00B3H
Option Code Connected to CN5-C
00B4H - 00BEH
Reserved
00BFH
Lists the last two digits of operation error code oPE.
00C0H
Fault Contents 3
bit 0
DC Fuse Blowout (PUF)
bit 1
Undervoltage (Uv1)
bit 2
Control Power Supply Undervoltage (Uv2)
bit 3
Soft Charge Circuit Fault (Uv3)
bit 4
IGBT Short Circuit (SC)
bit 5
Ground Fault (GF)
bit 6
Overcurrent (oC)
bit 7
Overvoltage (ov)
bit 8
Heatsink Overheat (oH)
bit 9
Overheat 1 (oH1)
bit A
Reserved
bit B
Converter Overload (oL2)
bit C - bit F
Reserved
00C1H
Fault Contents 4
bit 0
External Fault at input terminal S3 (EF3)
bit 1
External Fault at input terminal S4 (EF4)
bit 2
External Fault at input terminal S5 (EF5)
bit 3
External Fault at input terminal S6 (EF6)
bit 4
External Fault at input terminal S7 (EF7)
bit 5
External Fault at input terminal S8 (EF8)
bit 6
Cooling Fan Error (Fan)
bit 7 - bit C
Reserved
bit D
Digital Operator Connection Fault (oPr)
bit E
EEPROM Write Error (Err)
bit F
Reserved
00C2H
Fault Contents 5
bit 0
MEMOBUS/Modbus Communication Error (CE)
bit 1
Option Communication Error (bUS)
bit 2 - bit 5
Reserved
bit 6
Option External Fault (EF0)
bit 7 - bit E
Reserved
bit F
Hardware Fault (includes oF)
00C3H
Fault Contents 6
bit 0 - bit 7
Reserved
bit 8
MECHATROLINK Watchdog Timer Error (E5)
bit 9 - bit F
Reserved
Register No.
Contents
TOEP_C710656_07C_2_0.book 223 ページ 2015年1月9日 金曜日 午後6時23分