6.3 Periodic Maintenance
The converter has Maintenance Monitors that keep track of component wear. This feature provides advance maintenance
warning and eliminates the need to shut down the entire system for unexpected problems. The converter allows the user to
check predicted maintenance periods for the components listed below.
• Cooling Fan, Circulation Fan, Control Board Cooling Fan
• Electrolytic Capacitors
• Inrush Prevention Circuit
For replacement parts, contact the distributor where the converter was purchased or contact Yaskawa directly.
◆ Replacement Parts
contains the estimated performance life of components that require replacement during the life of the converter.
Only use Yaskawa replacement parts for the appropriate model and revision.
Table 6.3 Estimated Performance Life
NOTICE: Estimated performance life based on specific usage conditions. These conditions are provided for the purpose of replacing
parts to maintain performance. Some parts may require more frequent replacement due to poor environments or rigorous use.
Usage conditions for estimated performance life:
Ambient temperature: Yearly average of
40°C (IP00/Open Type enclosure)
Load factor: 80% maximum
Operation time: 24 hours a day
NOTICE: Replace the cooling fan correctly according to instructions in this manual. Incorrect cooling fan mounting direction will prevent
sufficient cooling of the converter and could damage internal circuits.
■
Performance Life Monitors Maintenance Monitors
The converter calculates the maintenance period for components that may require replacement during the life of the
converter. A percentage of the maintenance period is displayed on the digital operator by viewing the appropriate monitor
parameter.
When the maintenance period reaches 100%, there is increased risk that the converter may malfunction. Yaskawa
recommends checking the maintenance period regularly to ensure maximum performance life.
for more details.
Table 6.4 Performance Life Monitors Used for Component Replacement
Component
Estimated Performance Life
Cooling Fan, Circulation, Control Board Cooling Fan
<1> The converter has few serviceable parts and may require complete converter replacement.
10 years
Electrolytic Capacitors
10 years
Fuse
10 years
Parameter
Component
Contents
U4-03
Cooling Fan
Circulation Fan
Control Board Cooling Fan
Displays the accumulated operation time of the fan from 0 to 99999 hours. This value is
automatically reset to 0 after it reaches 99999.
U4-04
Displays the accumulated fan operation time as a percentage of the specified
maintenance period.
U4-05
DC Bus Capacitors
Displays the accumulated time the capacitors are used as a percentage of the specified
maintenance period.
U4-06
Inrush (pre-charge) Relay
Displays the number of times the converter is powered up as a percentage of the
performance life of the inrush circuit.