Yaskawa D1000 Series Power Regenerative Converter User Manual
Page 250

D.3 UL Standards
250
YASKAWA ELECTRIC TOEP C710656 07C YASKAWA Power Regenerative Converter - D1000 Instruction Manual
4A0040
R/L1, S/L2, T/L3
4
4 to 2/0
M8
5.4 to 6.0
(47.8 to 53.1)
,
4
4 to 2/0
M8
5.4 to 6.0
(47.8 to 53.1)
r1/ 11, 1/ 21, t1/ 31
14
14 to 10
M4
1.1 to 1.2
(9.7 to 10.6)
6
6
M8
9.0 to 11
(79.7 to 97.4)
4A0060
R/L1, S/L2, T/L3
2
2 to 2/0
M8
5.4 to 6.0
(47.8 to 53.1)
,
2
2 to 2/0
M8
5.4 to 6.0
(47.8 to 53.1)
r1/ 11, 1/ 21, t1/ 31
14
14 to 10
M4
1.1 to 1.2
(9.7 to 10.6)
6
6
M10
18 to 23
(159 to 204)
4A0100
R/L1, S/L2, T/L3
3
× 2P
3 to 2/0
M8
5.4 to 6.0
(47.8 to 53.1)
,
1/0
× 2P
1/0 to 2/0
M8
5.4 to 6.0
(47.8 to 53.1)
r1/ 11, 1/ 21, t1/ 31
14
14 to 10
M4
1.1 to 1.2
(9.7 to 10.6)
3
3
M10
18 to 23
(159 to 204)
4A0130
R/L1, S/L2, T/L3
3/0
× 2P
3/0 to 600
M10
18 to 23
(159 to 204)
,
3/0
× 2P
3/0 to 600
M10
18 to 23
(159 to 204)
r1/ 11, 1/ 21, t1/ 31
14
14 to 10
M4
1.1 to 1.2
(9.7 to 10.6)
1/0
1/0 to 2/0
M10
18 to 23
(159 to 204)
4A0185
R/L1, S/L2, T/L3
3/0
× 2P
3/0 to 600
M12
32 to 40
(283 to 354)
,
3/0
× 2P
3/0 to 600
M12
32 to 40
(283 to 354)
r1/ 11, 1/ 21, t1/ 31
14
14 to 10
M4
1.1 to 1.2
(9.7 to 10.6)
1/0
1/0 to 4/0
M12
32 to 40
(283 to 354)
4A0270
R/L1, S/L2, T/L3
300
× 2P
300
M12
32 to 40
(283 to 354)
,
300
× 2P
300
M12
32 to 40
(283 to 354)
r1/ 11, 1/ 21, t1/ 31
14
14 to 10
M4
1.1 to 1.2
(9.7 to 10.6)
2/0
2/0 to 4/0
M12
32 to 40
(283 to 354)
Model
Terminal
Recomm. Gauge
AWG, kcmil
Applicable Gauge
AWG, kcmil
Screw Size
Tightening Torque
Nm (lbin.)
– +
– +
– +
– +
– +
– +
TOEP_C710656_07C_2_0.book 250 ページ 2015年1月9日 金曜日 午後6時23分