Yaskawa D1000 Series Power Regenerative Converter User Manual
Page 129

5.5 Operator Programming Errors
YASKAWA ELECTRIC TOEP C710656 07C YASKAWA Power Regenerative Converter - D1000 Instruction Manual
129
Tr
ou
blesh
oot
ing
5
Digital Operator
Display
Error Name
Detail
oPE04
Terminal Board
Mismatch Error
The converter or the removable terminal block with parameter backup was replaced.
Cause
Possible Solutions
The converter was replaced (but the removable
terminal block with parameter backup was not
replaced).
Set A1-03 to 5550 to load the parameter settings stored in the terminal board to the converter.
Initialize parameters after converter replacement by setting A1-03 to 2220.
The removable terminal block with parameter
backup was replaced.
Digital Operator
Display
Error Name
Detail
oPE05
Run Command
Selection Error
The settings for the Run Command or Bus Voltage Command are not correct.
Cause
Possible Solutions
The Run command is assigned to an option card
(b1-18 = 3) and an input option card is not
connected to the converter.
Reconnect the input option card to the converter.
The Run command is assigned to an option card
(b1-02 = 3) and an input option card is not
connected to the converter.
Digital Operator
Display
Error Name
Detail
oPE07
Multi-Function Analog
Input Selection Error A contradictory setting is assigned to multi-function analog inputs H3-02, H3-10, or H3-06.
Cause
Possible Solutions
At least two of these parameters have the same
setting: H3-02, H3-10, or H3-06.
Change the settings to H3-02, H3-10, and H3-06 so that functions no longer conflict.
Note: Both 1F (Through mode) and F (Through mode) can be set to H3-02, H3-10, or H3-06
simultaneously.
Digital Operator
Display
Error Name
Detail
oPE30
Incorrect Input Voltage
Adjustment
The input voltage offset adjustment has not been performed.
Cause
Possible Solutions
• The setting of o2-04 (Drive Model Selection)
changed.
• ERPROM failed for the input voltage offset.
For information on clearing the fault, consult with your Yaskawa representative or the nearest
Yaskawa sales office.
TOEP_C710656_07C_2_0.book 129 ページ 2015年1月9日 金曜日 午後6時23分