3 harmonic filter module installation, Installation environment, Harmonic filter module installation – Yaskawa D1000 Series Power Regenerative Converter User Manual
Page 39

2.3 Harmonic Filter Module Installation
YASKAWA ELECTRIC TOEP C710656 07C YASKAWA Power Regenerative Converter - D1000 Instruction Manual
39
Mec
h
an
ic
al
In
st
al
la
tio
n
2
2.3 Harmonic Filter Module Installation
◆ Installation Environment
Install the harmonic filter module in an environment matching the specifications in
to help prolong the optimum
performance life of the harmonic filter module.
Table 2.8 Installation Environment
WARNING! Fire Hazard. When installing an IP00/IP20 converter in a closed panel or cabinet, sufficiently cool the panel or cabinet with
a cooling fan or air conditioner so that the air temperature entering the converter is 50
°C (122 °F) or cooler. Failure to comply could
result in overheating and fire.
NOTICE: Avoid placing converter peripheral devices, transformers, or other electronics near the converter as the noise created can
lead to erroneous operation. If such devices must be used in close proximity to the converter, take proper steps to shield the converter
from noise.
NOTICE: Prevent foreign matter such as metal shavings and wire clippings from falling into the converter and harmonic filter module
during installation. Failure to comply could result in damage to the converter and the harmonic filter module. Place a temporary cover
over the top of the converter and the harmonic filter module during installation. Remove the temporary cover before converter and
harmonic filter module start-up, as the cover will reduce ventilation and cause the converter and the harmonic filter module to overheat.
Environment
Conditions
Installation Area
Indoors
Install the converter in an environment that does not easily accessible such as control panel.
Ambient
Temperature
IP00/Open Type enclosure: -10
°C to +50°C (14°F to 140°F)
Harmonic filter module reliability improves in environments without wide temperature fluctuations.
When using the harmonic filter module in an enclosure panel, install a cooling fan or air conditioner in the area to ensure
that the air temperature inside the enclosure does not exceed the specified levels.
Do not allow ice to develop on the harmonic filter module.
Humidity
95% RH or less and free of condensation
Storage
Temperature
-20
°C to +60°C (-4°F to +140°F)
Surrounding Area
Install the harmonic filter module in an area free from:
• oil mist and dust
• metal shavings, oil, water, or other foreign materials
• radioactive materials
• combustible materials (e.g., wood)
• harmful gases and liquids
• excessive vibration
• chlorides
• direct sunlight.
Altitude
3000 m (9843 ft) or lower
Vibration
2.0 m/s
2
(20 to 55 Hz)
TOEP_C710656_07C_2_0.book 39 ページ 2015年1月9日 金曜日 午後6時23分