5.1 Section Safety
5.1 Section Safety
W ARNING
Electrical Shock Hazard
If a fuse is open or ground fault circuit interrupter GFCI is tripped, check the wiring and the selection of the
peripheral devices.
Contact your supplier if the cause cannot be identified. Failure to comply may result in electrical shock by indirect or
direct contact. The converter can cause a residual current with a DC component in the protective earthing conductor.
After blowing a fuse or ground fault circuit interrupter GFCI is tripped, do not attempt to restart the converter
or operate peripheral devices until five minutes pass and CHARGE lamp is OFF.
Failure to comply could result in death, serious injury, and damage to the converter.
Do not connect or disconnect wiring while the power is on.
Failure to comply could result in death or serious injury.
Before servicing, disconnect all power to the equipment. The internal capacitor remains charged even after the power
supply is turned off. The charge indicator LED will extinguish when the DC bus voltage is below 50 Vdc. To prevent
electric shock, wait for at least the time specified on the warning label; after all indicators are OFF, measure for unsafe
voltages to confirm the converter is safe prior to servicing.
Do not operate equipment with covers removed.
Failure to comply could result in death or serious injury.
The diagrams in this section may illustrate converter without covers or safety shields to display details. Be sure to
reinstall covers or shields before operating the converter and run the converter according to the instructions described
in this manual.
Do not touch terminals before the capacitors have fully discharged.
Failure to comply could result in death or serious injury.
Before servicing, disconnect all power to the equipment. The internal capacitor remains charged even after the power
supply is turned off. The charge indicator LED will extinguish when the DC bus voltage is below 50 Vdc. To prevent
electric shock, wait for at least the time specified on the warning label; after all indicators are OFF, measure for unsafe
voltages to confirm the converter is safe prior to servicing.
Do not allow unqualified personnel to perform work on the converter.
Failure to comply could result in death or serious injury.
Installation, maintenance, inspection and servicing must be performed only by authorized personnel familiar with
installation, adjustment and maintenance this equipment.
Do not perform work on the converter while wearing loose clothing, jewelry, or without eye protection.
Failure to comply could result in death or serious injury.
Remove all metal objects such as watches and rings, secure loose clothing and wear eye protection before beginning
work on the converter.
Do not remove covers or touch circuit boards while the power is on.
Failure to comply could result in death or serious injury.