B: application – Yaskawa D1000 Series Power Regenerative Converter User Manual
Page 182

B.2 Parameter Tables
182
YASKAWA ELECTRIC TOEP C710656 07C YASKAWA Power Regenerative Converter - D1000 Instruction Manual
◆ b: Application
Application parameters configure the source of the operation mode selection.
No.
(Address
Hex)
Name
LCD Display
Description
Values
b1: Operation Mode Selection
b1-02
(181H)
Run Command
Selection 1
Run Source 1
0: Digital operator
1: Digital Inputs
2: Communication
3: Option PCB
0: Digital operator
1: Digital input terminals
2: MEMOBUS/Modbus communications
3: Option PCB
Default: 1
Range: 0 to 3
b1-06
(185H)
Digital Input
Reading
Cntl Input Scans
1: Scan
2: Scans
Defines how the digital inputs are read. The inputs are
acted upon every 1 ms or 2 ms depending upon the setting.
0: Input status is read once and processed immediately (for
quicker response)
1: Input is read twice and processed only if the status is the
same in both readings (robust against noisy signals)
Default: 1
Range: 0, 1
b1-08
(187H)
Run Command
Selection in
Programming Mode
RUN dur PRG Mode
0: Run
Disabled@PRG
1: ModeRun
Enabled@PRG
2: Prg only @ Stop
Allow the converter to run while in Programming Mode.
0: Run command is not accepted while in Programming
Mode.
1: Run command is accepted while in Programming Mode.
2: Prohibit entering Programming Mode during run.
Default: 0
Range: 0 to 2
b1-17
(1C6H)
Run Command at
Power Up
Run Cmd @ Pwr On
0: Cycle Ext Run
1: Accept Ext Run
Determines whether an external Run command that is
active during power up will start the converter.
0: Disregarded. A new Run Command must be issued.
1: Allowed. Converter will start immediately if Run
Command is present at power up.
Default: 0
Range: 0, 1
b1-18
(179H)
Voltage Reference
Source
Reference Sel
0: Operator
1: Analog Input
2: Serial Com
3: Option PCB
7: AutoMode1
8: AutoMode2
Sets the input source for the voltage reference.
0: Digital operator
1: Control circuit terminal (analog input)
2: MEMOBUS/Modbus communications
3: Option card
7: Input voltage based control 1
8: Input voltage based control 2
Default: 0
Range: 0 to 8
b4: Timer Function
b4-01
(1A3H)
Timer Function
On-Delay Time
Delay-ON Timer
Sets the on-delay times for a digital timer output (H2-
= 12).
The output is triggered by a digital input programmed to
H1- = 18.
Default: 0.0 s
Min.: 0.0 s
Max.: 3000.0 s
b4-02
(1A4H)
Timer Function
Off-Delay Time
Delay-OFF Timer
Sets the off-delay times for a digital timer output (H2-
= 12).
The output is triggered by a digital input programmed to
H1- = 18.
Default: 0.0 s
Min.: 0.0 s
Max.: 3000.0 s