Monitor data – Yaskawa D1000 Series Power Regenerative Converter User Manual
Page 220

C.9 MEMOBUS/Modbus Data Table
220
YASKAWA ELECTRIC TOEP C710656 07C YASKAWA Power Regenerative Converter - D1000 Instruction Manual
◆ Monitor Data
Monitor data can be read only.
Register No.
Contents
0020H
Converter Status 1
bit 0
During Run
bit 1
Reserved
bit 2
Operation Ready
bit 3
Fault
bit 4
Data Setting Error
bit 5
Multi-Function Relay Output (terminal M1-M2)
bit 6
Multi-Function Relay Output 1 (terminal M3-M4)
bit 7
Multi-Function Relay Output 2 (terminal M5-M6)
bit 8 - bit F
Reserved
0021H
Fault Contents 1
bit 0
Overcurrent (oC), Ground fault (GF)
bit 1
Overvoltage (ov)
bit 2
Converter Overload (oL2)
bit 3
Overheat 1 (oH1), Overheat 2 (oH2)
bit 4 - bit 6
Reserved
bit 7
EF to EF8: External Fault
bit 8
CPF: Hardware Fault (includes oF)
bit 9 - bit A
Reserved
bit B
Main Circuit Undervoltage (Uv)
bit C
Undervoltage (Uv1), Control Power Supply Undervoltage (Uv2), Soft Charge Circuit Fault
(Uv3)
bit D
Output Phase Loss (LF), Input Phase Loss (PF)
bit E
MEMOBUS/Modbus Communication Error (CE), Option Communication Error (bUS)
bit F
Operator Connection Fault (oPr)
0022H
Data Link Status
bit 0
Writing data or switching motors
bit 1 - bit 2
Reserved
bit 3
Upper or lower limit error
bit 4
Data conformity error
bit 5
Writing to EEPROM
bit 6 - bit F
Reserved
0023H - 0028H
Reserved
0029H
Fault Contents 2
bit 0
Reserved
bit 1
Ground Fault (GF)
bit 2 - bit F
Reserved
TOEP_C710656_07C_2_0.book 220 ページ 2015年1月9日 金曜日 午後6時23分