5 operator programming errors, Operator programming errors – Yaskawa D1000 Series Power Regenerative Converter User Manual
Page 128

128
YASKAWA ELECTRIC TOEP C710656 07C YASKAWA Power Regenerative Converter - D1000 Instruction Manual
5.5 Operator Programming Errors
5.5 Operator Programming Errors
◆ Operator Programming Error Codes, Causes, and Possible Solutions
An Operator Programming Error (oPE) occurs when a contradictory parameter is set or an individual parameter is set to
an inappropriate value.
The converter will not operate until the parameter or parameters causing the problem are set correctly. An oPE, however,
does not trigger an alarm or fault output. If an oPE occurs, investigate the cause and refer to
for the appropriate
action. When an oPE appears on the operator display, press the ENTER button to view U1-18 and see which parameter is
causing the oPE.
Table 5.8 oPE Codes, Causes, and Possible Solutions
Digital Operator
Display
Error Name
Detail
Err
EEPROM Write Error A verification mismatch occurred when writing data to the EEPROM.
Cause
Possible Solutions
The data was corrupted by noise when writing
data to the EEPROM.
• Press .
• Set the parameters again.
• Cycle the power supply. Refer to
Diagnosing and Resetting Faults on page 131
for details.
EEPROM Hardware Failure
Replace the board or converter. For information on board replacement, consult with your
Yaskawa representative or the nearest Yaskawa sales office.
Digital Operator
Display
Error Name
Detail
oPE01
Converter Capacity
Setting Fault
Converter capacity and the value set to o2-04 do not match.
Cause
Possible Solutions
The drive model selection (o2-04) and the
actual capacity of the converter are not the
same.
Correct the value set to o2-04.
Digital Operator
Display
Error Name
Detail
oPE02
Parameter Range
Setting Error
Use U1-18 to find parameters set outside the range.
Cause
Possible Solutions
Parameters were set outside the possible setting
range.
Set parameters to the proper values.
Note: When multiple errors occur simultaneously, other errors are given precedence over oPE02.
Digital Operator
Display
Error Name
Detail
oPE03
Multi-Function Input
Selection Error
A contradictory setting is assigned to multi-function contact inputs H1-01 to H1-08.
Cause
Possible Solutions
The same function is assigned to two
multi-function inputs. Excludes “Not used” and
“External Fault.”
• Ensure all multi-function inputs are assigned to different functions.
• Re-enter the multi-function settings to ensure this does not occur.
TOEP_C710656_07C_2_0.book 128 ページ 2015年1月9日 金曜日 午後6時23分