beautypg.com

Yaskawa D1000 Series Power Regenerative Converter User Manual

Page 248

background image

D.3 UL Standards

248

YASKAWA ELECTRIC TOEP C710656 07C YASKAWA Power Regenerative Converter - D1000 Instruction Manual

Wire Gauges and Tightening Torques

Table D.5 Wire Gauge and Torque Specifications (Three-Phase 200 V Class)

Model

Terminal

Recomm. Gauge

AWG, kcmil

Applicable Gauge

AWG, kcmil

Screw Size

Tightening Torque

Nm (lbin.)

2A0005

R/L1, S/L2, T/L3

12

12 to 6

M4

2.1 to 2.3

(18.6 to 20.4)

,

12

12 to 6

M4

2.1 to 2.3

(18.6 to 20.4)

r1/ 11, 1/ 21,

t1/ 31

14

14

M3.5

0.8 to 1.0

(7.1 to 8.9)

10

16 to 10

M6

5.4 to 6.0

(47.8 to 53.1)

2A0010

R/L1, S/L2, T/L3

8

8 to 6

M4

2.1 to 2.3

(18.6 to 20.4)

,

8

8 to 6

M4

2.1 to 2.3

(18.6 to 20.4)

r1/ 11, 1/ 21,

t1/ 31

14

14

M3.5

0.8 to 1.0

(7.1 to 8.9)

10

12 to 10

M6

5.4 to 6.0

(47.8 to 53.1)

2A0020

R/L1, S/L2, T/L3

4

4 to 1

M6

3.6 to 4.0

(31.9 to 35.4)

,

4

4 to 1

M6

3.6 to 4.0

(31.9 to 35.4)

r1/ 11, 1/ 21,

t1/ 31

14

14

M3.5

0.8 to 1.0

(7.1 to 8.9)

6

8 to 6

M6

5.4 to 6.0

(47.8 to 53.1)

2A0030

R/L1, S/L2, T/L3

2

2 to 2/0

M8

5.4 to 6.0

(47.8 to 53.1)

,

2

2 to 2/0

M8

5.4 to 6.0

(47.8 to 53.1)

r1/ 11, 1/ 21, t1/ 31

14

14 to 10

M4

1.1 to 1.2

(9.7 to 10.6)

4

6 to 4

M8

9.0 to 11

(79.7 to 97.4)

2A0050

R/L1, S/L2, T/L3

3

× 2P

3 to 2/0

M8

5.4 to 6.0

(47.8 to 53.1)

,

1/0

× 2P

1/0 to 2/0

M8

5.4 to 6.0

(47.8 to 53.1)

r1/ 11, 1/ 21, t1/ 31

14

14 to 10

M4

1.1 to 1.2

(9.7 to 10.6)

4

4

M10

18 to 23

(159 to 204)

2A0065

R/L1, S/L2, T/L3

3/0

× 2P

3/0 to 300

M12

32 to 40

(283 to 354)

,

3/0

× 2P

3/0 to 300

M12

32 to 40

(283 to 354)

r1/ 11, 1/ 21, t1/ 31

14

14 to 10

M4

1.1 to 1.2

(9.7 to 10.6)

1

1 to 1/0

M12

32 to 40

(283 to 354)

– +

– +

– +

– +

– +

– +

TOEP_C710656_07C_2_0.book 248 ページ 2015年1月9日 金曜日 午後6時23分