beautypg.com

Yaskawa D1000 Series Power Regenerative Converter User Manual

Page 185

background image

B.2 Parameter Tables

YASKAWA ELECTRIC TOEP C710656 07C YASKAWA Power Regenerative Converter - D1000 Instruction Manual

185

Par

ame

te

r Li

st

B

F4-05

(395H)

Terminal V1
Monitor Bias

AO Ch1 Bias

Sets the amount of bias added to the voltage output via
terminal V1.

Default: 0.0%
Min.: -999.9%
Max.: 999.9%

F4-06

(396H)

Terminal V2
Monitor Bias

AO Ch2 Bias

Sets the amount of bias added to the voltage output via
terminal V2.

Default: 0.0%
Min.: -999.9%
Max.: 999.9%

F4-07

(397H)

Terminal V1 Signal
Level

AO Opt Level Ch1
0: 0-10 VDC
1: -10 +10 VDC

0: 0 to 10 V
1: -10 to 10 V

Default: 0
Min.: 0
Max.: 1

F4-08

(398H)

Terminal V2 Signal
Level

AO Opt Level Ch2
0: 0-10 VDC
1: -10 +10 VDC

0: 0 to 10 V
1: -10 to 10 V

Default: 0
Min.: 0
Max.: 1

F5: Digital Output Card (DO-A3)

F5-01

(399H)

Terminal P1-PC
Output Selection

DO Ch1 Select

Sets the function for contact output terminals M1-M2,
M3-M4, and photocoupler output terminals P1 through P6.

Default: F
Min.: 0
Max.: 160

F5-02

(39AH)

Terminal P2-PC
Output Selection

DO Ch2 Select

Default: F
Min.: 0
Max.: 160

F5-03

(39BH)

Terminal P3-PC
Output Selection

DO Ch3 Select

Default: F
Min.: 0
Max.: 160

F5-04

(39CH)

Terminal P4-PC
Output Selection

DO Ch4 Select

Default: F
Min.: 0
Max.: 160

F5-05

(39DH)

Terminal P5-PC
Output Selection

DO Ch5 Select

Default: F
Min.: 0
Max.: 160

F5-06

(39EH)

Terminal P6-PC
Output Selection

DO Ch6 Select

Default: F
Min.: 0
Max.: 160

F5-07

(39FH)

Terminal M1-M2
Output Selection

DO Ch7 Select

Default: F
Min.: 0
Max.: 160

F5-08

(3A0H)

Terminal M3-M4
Output Selection

DO Ch8 Select

Default: F
Min.: 0
Max.: 160

F6: Communication Option Card

For details on a specific option card, refer to the instruction manual for the option card.

No.

(Address

Hex)

Name

LCD Display

Description

Values

TOEP_C710656_07C_2_0.book 185 ページ 2015年1月9日 金曜日 午後6時23分