B.2 Parameter Tables

192

YASKAWA ELECTRIC TOEP C710656 07C YASKAWA Power Regenerative Converter - D1000 Instruction Manual

L8: Drive Protection

L8-02

(4AEH)

Overheat Alarm
Level

OH Pre-Alarm Lvl

An overheat alarm occurs when heatsink temperature
exceeds the L8-02 level.

Default:

<2>

Min.: 50

°C

Max.: 150

°C

L8-03

(4AFH)

Overheat Pre-Alarm
Operation Selection

OH Pre-Alarm Sel
1: Ramp to stop
3: Alarm only

1: Ramp to stop. A fault is triggered.
3: Continue operation. An alarm is triggered.

Default: 3
Min.: 1
Max.: 3

L8-09

(4B5H)

Output Ground Fault
Detection Selection

Grnd Flt Det Sel
0: Disabled
1: Enabled

0: Disabled
1: Enabled

Default:

<2>

Min.: 0
Max.: 1

L8-10

(4B6H)

Heatsink Cooling
Fan Operation
Selection

Fan On/Off Sel
0: Dur Run (OffDly)
1: Always On

0: During run only. Fan operates only during run for L8-11
seconds after stop.
1: Fan always on. Cooling fan operates whenever the
converter is powered up.

Default: 0
Min.: 0
Max.: 1

L8-11

(4B7H)

Heatsink Cooling
Fan Off Delay Time

Fan Delay Time

Sets a delay time to shut off the cooling fan after the Run
command is removed when L8-10 = 0.

Default: 60 s
Min.: 0 s
Max.: 300 s

L8-12

(4B8H)

Ambient
Temperature Setting

Ambient Temp

Enter the ambient temperature. This value adjusts the oL2
detection level.

Default: 40

°C

Min.: -10

°C

Max.: 50

°C

L8-35

(4ECH)

Installation Method
Selection

Installation Sel
0: IP00/OpenChassis
1: Side-by-Side
3: ExternalHeatsink

0: IP00/IP20/Open Type Enclosure
1: Side-by-Side Mounting
3: External Heatsink Installation

Default:

<2>

Min.: 0
Max.: 3

L8-41

(4F2H)

High Current Alarm
Selection

High Cur Alm Sel
0: Disabled
1: Enabled

0: Disabled
1: Enabled. An alarm is triggered at output currents above
150% of converter rated current.

Default: 0
Min.: 0
Max.: 1

L8-65

(66FH)

Power Supply Fault
Detection Selection

Vpn Ripple Sel
0: Disabled
1: Coast to Stop
2: Alarm Only

There is normally no need to change this parameter from
the default value.
Monitors the ripple of DC BUS voltage and detects Input
Power Supply Fault(PF2) when the ripple is too bad.
0: No detection
1: Stop operation (fault)
2: Continue operation (minor fault)

Default: 0
Min.: 0
Max.: 2

L8-66

(670H)

Power Supply Fault
Detection Voltage
Level

Vpn Ripple Lvl

There is normally no need to change this parameter from
the default value. The main circuit DC voltage ripple is
monitored in a cycle of 200 ms. If the difference between
the maximum and minimum values of the ripple exceeds
the value that is set in L8-66 for the number of times that is
set in L8-67, a power supply fault is detected.

200V Class

Default:

<2>

Min.: 1
Max.: 200

400V Class

Default:

<2>

Min.: 1
Max.: 200

L8-67

(671H)

Number of Times of
Power Supply Fault
for Detection

Vpn Ripple Cnt

Default: 5
Min.: 1
Max.: 10

L8-69

(673H)

Input Phase Loss
Protection Selection
3

AC Phase Imb Det
0: Disabled
1: Enabled

Sets whether to enable or disable the protective function
for the converter when there is an input phase loss.
0: Disabled
1: Enabled (Detect input phase loss and power supply
imbalance.)

Default: 1
Min.: 0
Max.: 1

L8-78

(2CCH)

Module Phase Loss
(LF3) Protection

LF3 Det Sel
0: Disabled
1: Enabled

Enables phase loss protection for the input terminals R/L1,
S/L2, T/L3 or R1/L11, S1/L21, T1/L31.
0: Disable
1: Enable
Note: This parameter is available only in model 4A0630.

Default: 1
Min.: 0
Max.: 1

No.

(Address

Hex)

Name

LCD Display

Description

Values