4.6 Verifying Parameter Settings and Backing Up Changes

YASKAWA ELECTRIC TOEP C710656 07C YASKAWA Power Regenerative Converter - D1000 Instruction Manual

101

S

ta

rt

-Up Pr

ogr

amming

&

O

p

er

at

io

n

4

Copying Procedure for the LCD Operator

The LCD operator can perform the following operations by changing the o3-01(Copy Function Selection) parameter in
the converter.

Read (o3-01 = 1)

Copies all parameters from the converter to the LCD operator.

Note: There is a limit to the number of read operations that you can perform from the LCD operator. As a guide, do not perform more

than 100,000 read operations.

Copy (o3-01 = 2)

Copies all parameters from the LCD operator to the converter.

Verify (o3-01 = 3)

Compares the parameters in the converter with the parameter settings saved on the LCD operator for matches.

TOEP_C710656_07C_2_0.book 101 ページ 2015年1月9日 金曜日 午後6時23分