D.3 UL Standards
YASKAWA ELECTRIC TOEP C710656 07C YASKAWA Power Regenerative Converter - D1000 Instruction Manual
249
St
and
ar
ds Co
mpl
ia
nce
D
Table D.6 Wire Gauge and Torque Specifications (Three-Phase 400 V Class)
2A0090
R/L1, S/L2, T/L3
3/0
× 2P
3/0 to 300
M12
32 to 40
(283 to 354)
,
3/0
× 2P
3/0 to 300
M12
32 to 40
(283 to 354)
r1/ 11, 1/ 21, t1/ 31
14
14 to 10
M4
1.1 to 1.2
(9.7 to 10.6)
1/0
1/0 to 4/0
M12
32 to 40
(283 to 354)
2A0130
R/L1, S/L2, T/L3
300
× 2P
300 to 600
M12
32 to 40
(283 to 354)
,
300
× 2P
300 to 600
M12
32 to 40
(283 to 354)
r1/ 11, 1/ 21, t1/ 31
14
14 to 10
M4
1.1 to 1.2
(9.7 to 10.6)
2/0
2/0 to 4/0
M12
32 to 40
(283 to 354)
Model
Terminal
Recomm. Gauge
AWG, kcmil
Applicable Gauge
AWG, kcmil
Screw Size
Tightening Torque
Nm (lbin.)
4A0005
R/L1, S/L2, T/L3
12
12 to 6
M4
2.1 to 2.3
(18.6 to 20.4)
,
12
12 to 6
M4
2.1 to 2.3
(18.6 to 20.4)
r1/ 11, 1/ 21,
t1/ 31
14
14
M3.5
0.8 to 1.0
(7.1 to 8.9)
12
14 to 12
M6
5.4 to 6.0
(47.8 to 53.1)
4A0010
R/L1, S/L2, T/L3
12
12 to 6
M4
2.1 to 2.3
(18.6 to 20.4)
,
12
12 to 6
M4
2.1 to 2.3
(18.6 to 20.4)
r1/ 11, 1/ 21,
t1/ 31
14
14
M3.5
0.8 to 1.0
(7.1 to 8.9)
10
12 to 10
M6
5.4 to 6.0
(47.8 to 53.1)
4A0020
R/L1, S/L2, T/L3
8
8 to 1
M6
3.6 to 4.0
(31.9 to 35.4)
,
8
8 to 1
M6
3.6 to 4.0
(31.9 to 35.4)
r1/ 11, 1/ 21,
t1/ 31
14
14
M3.5
0.8 to 1.0
(7.1 to 8.9)
8
10 to 8
M6
5.4 to 6.0
(47.8 to 53.1)
4A0030
R/L1, S/L2, T/L3
6
6 to 2/0
M8
5.4 to 6.0
(47.8 to 53.1)
,
6
6 to 2/0
M8
5.4 to 6.0
(47.8 to 53.1)
r1/ 11, 1/ 21, t1/ 31
14
14 to 10
M4
1.1 to 1.2
(9.7 to 10.6)
6
8 to 6
M8
9.0 to 11
(79.7 to 97.4)
Model
Terminal
Recomm. Gauge
AWG, kcmil
Applicable Gauge
AWG, kcmil
Screw Size
Tightening Torque
Nm (lbin.)
– +
– +
– +
– +
– +
– +
TOEP_C710656_07C_2_0.book 249 ページ 2015年1月9日 金曜日 午後6時23分