5.6 Copy Function Related Displays

5.6 Copy Function Related Displays

Tasks, Errors, and Troubleshooting

The table below lists the messages and errors that may appear when using the Copy function. When executing the tasks
offered by the Copy function, the operator will indicate the task being performed. When an error occurs, a code appears
on the operator to indicate the error. Note that errors related to the Copy function do not trigger a multifunction output
terminal that has been set up to close when a fault or alarm occurs. To clear an error, simply press any key on the operator
and the error display will disappear.

Table 5.9

lists the corrective action that can be taken when an error occurs.

Note: 1. Whenever using the copy function, the converter should be fully stopped.

2. The converter will not accept a Run command while the Copy function is being executed.
3. Parameters can only be saved to a converter when the voltage class, capacity, control mode, and software version match.

Table 5.9 Copy Function Task and Error Displays

Digital Operator Display

Error Name

CoPy

Writing Parameter Settings (flashing)

CPyE

Error Writing Data

CSEr

Copy Unit Error

dFPS

Model Mismatch

End

Task Complete

iFEr

Communication Error

ndAT

Model, Voltage Class, Capacity Mismatch

rdEr

Error Reading Data

rEAd

Reading Parameter Settings (flashing)

vAEr

Voltage Class, Capacity Mismatch

vFyE

Parameter settings in the converter and those saved to the copy function are not the same

vrFy

Comparing Parameter Settings (flashing)