◆ Alarm and Error Displays
■
Faults
gives an overview of possible fault codes. Conditions such as overvoltages can trip faults and alarms. It is
important to distinguish between faults and alarms to determine the proper corrective actions. When the converter detects
a fault, the ALM indicator LED lights, the fault code appears on the digital operator, and the fault contact MA-MB-MC
triggers. An alarm is present if the ALM LED blinks and the fault code on the digital operator flashes. Refer to
for a list of alarm codes.
Table 5.2 Fault Displays
Digital Operator
Display
Name
Page
Digital Operator
Display
Name
Page
LED
LCD
LED
LCD
Aov
Power Supply Overvoltage
FUA
AC Fuse Blowout
AUv
Power Supply Undervoltage
FUd
DC Fuse Blowout
bUS
Option Communication Error
GF
Ground Fault
CE
MEMOBUS/Modbus
Communication Error
nSE
Node Setup Error
CoF
Current Offset Fault
oC
Overcurrent
,
CPF00,
CPF01
Control Circuit Error
to
oFA00 to
oFA43
Option Card Fault (CN5-A)
CPF02
A/D Conversion Error
CPF03
Control Board Connection
Error
to
oFb00 to
oFb17
Option Card Fault (CN5-B)
CPF06
EEPROM Memory Data Error
CPF07
Terminal Board Connection
Error
to
oFC00 to
oFC55
Option Card Fault (CN5-C)
CPF08
Terminal Board Connection
Error
,
CPF11 to
CPF22
Control Circuit Error
oH
Heatsink Overheat
oH1
Overheat 1
CPF23
Control Board Connection
Error
oL2
Converter Overload
CPF24
Unit Capacity Detect Fault
oPr
Operator Connection Fault
to
CPF26
to
CPF35
Control Circuit Error
ov
Overvoltage
PF2
Input Power Supply Fault
E5
MECHATROLINK
Watchdog Timer Error
PF3
Input Phase Loss Detection
EF0
Option Card External Fault
SC
IGBT Short Circuit or Ground
Fault
to
EF1
to
EF8
External Fault
(input terminal S1 to S8)
SrC
Phase Order Fault
Uv1
Main Circuit Undervoltage
Err
EEPROM Write Error
Uv2
Control Power Supply
Undervoltage
Fan
Internal Fan Fault
Uv3
Soft Charge Circuit Fault
Fdv
Power Supply Frequency Fault
vrE
Resonance Detection
TOEP_C710656_07C_2_0.book 106 ページ 2015年1月9日 金曜日 午後6時23分