C.9 MEMOBUS/Modbus Data Table
YASKAWA ELECTRIC TOEP C710656 07C YASKAWA Power Regenerative Converter - D1000 Instruction Manual
221
MEMO
BUS/Mod
bus
Co
mmunica
tion
s
C
002AH
Alarm Contents 1
bit 0 - bit 2
Reserved
bit 3
Drive Baseblock (bb)
bit 4
Reserved
bit 5
Heatsink Overheat (oH)
bit 6
Overvoltage (ov)
bit 7
Undervoltage (Uv)
bit 8
Cooling Fan Error (Fan)
bit 9
MEMOBUS/Modbus Communication Error (CE)
bit A
Option Communication Error (bUS)
bit B - bit E
Reserved
bit F
Serial Communication Transmission Error (CALL)
002BH
Input Terminal Status
bit 0
Terminal S1 Closed
bit 1
Terminal S2 Closed
bit 2
Terminal S3 Closed
bit 3
Terminal S4 Closed
bit 4
Terminal S5 Closed
bit 5
Terminal S6 Closed
bit 6
Terminal S7 Closed
bit 7
Terminal S8 Closed
bit 8 - bit F
Reserved
002CH
Drive Status 2
bit 0
During Run
bit 1 - bit 5
Reserved
bit 6
Drive Ready
bit 7
During Undervoltage
bit 8
During Baseblock
bit 9
Voltage Reference from Operator Keypad
bit A
Run Command from Operator Keypad
bit B - bit C
Reserved
bit D
During Fault Restart
bit E
Fault
bit F
Communication Timeout
002DH
Output Terminal Status
bit 0
Multi-Function Relay Output 1 (terminal M1-M2)
bit 1
Multi-Function Relay Output 1 (terminal M3-M4)
bit 2
Multi-Function Relay Output 2 (terminal M5-M6)
bit 3 - bit 6
Reserved
bit 7
Fault Contact Output (terminal MA/MB-MC)
bit 8 - bit F
Reserved
Register No.
Contents