4 standard configuration devices wiring, Wire gauges and tightening torque, Standard configuration devices wiring – Yaskawa D1000 Series Power Regenerative Converter User Manual
Page 168: Harmonic filter module

168
YASKAWA ELECTRIC TOEP C710656 07C YASKAWA Power Regenerative Converter - D1000 Instruction Manual
7.4 Standard Configuration Devices Wiring
7.4 Standard Configuration Devices Wiring
Install the standard configuration devices according to
when installing the converter.
For more information, refer to
Standard Connection Diagram on page 48
. Refer to the product catalog for selection of
standard configuration devices.
Table 7.2 Standard Configuration Devices (200 V Class)
Table 7.3 Standard Configuration Devices (400 V Class)
◆ Wire Gauges and Tightening Torque
Use the tables in this section to select the appropriate wires and crimp terminals.
Note: 1. Wire gauge recommendations based on continuous current ratings using 75
°C 600 Vac vinyl-sheathed wire assuming ambient
temperature within 40
°C.
2. Wire gauge recommendations for models 4A0270 to 4A0630 based on continuous current ratings using 105
°C 600 Vac vinyl sheathed
wire assuming ambient temperature within 40
°C.
Consider the amount of voltage drop when selecting wire gauges. Increase the wire gauge when the voltage drop is
greater than 2% of motor rated voltage. Ensure the wire gauge is suitable for the terminal block. Use the following
formula to calculate the amount of voltage drop:
Line drop voltage (V) =
× wire resistance (Ω/km) × wire length (m) × current (A) × 10
-3
■
Harmonic Filter Module
Refer to
Wire Gauges and Tightening Torque on page 69
when wiring of the harmonic filter module.
Voltage Class
200 V Class
Model
2A0005
2A0010
2A0020
2A0030
2A0050
2A0065
2A0090
2A0130
Harmonic Filter Module
Input-side AC Reactor 1
Input-side AC Reactor 2
–
–
–
–
–
–
–
–
Reactor for Harmonic Filter
–
–
–
–
–
–
–
–
Capacitor for Harmonic Filter
–
–
–
–
–
–
–
–
Voltage Class
400 V Class
Model
4A0005 4A0010 4A0020 4A0030 4A0040 4A0060 4A0100 4A0130 4A0185 4A0270 4A0370 4A0630
Harmonic Filter Module
–
–
–
Input-side AC Reactor 1
Input-side AC Reactor 2
–
–
–
–
–
–
–
–
–
Reactor for Harmonic Filter
–
–
–
–
–
–
–
–
–
Capacitor for Harmonic Filter
–
–
–
–
–
–
–
–
–
3
TOEP_C710656_07C_2_0.book 168 ページ 2015年1月9日 金曜日 午後6時23分