A.2 Converter Specifications
Item
Specification
Input
Rated Voltage
Rated Frequency
200 V Class: 200 to 240 Vac 50/60 Hz
400 V Class: 380 to 480 Vac 50/60 Hz
Allowable Voltage
Fluctuation
-15 to +10%
Allowable Frequency
Fluctuation
±2%
Control
Characteristics
Control Method
Sine-wave PWM control
Input Power Factor
Input power factor of 0.99 minimum (for rated operation)
Output Voltage Accuracy
±5%
Overload Protection
Converter stops after 60 s at 150% of rated output current or after 3 s at 200% of rated output
current.
Voltage Reference Range
200 V Class: 300 to 360 Vdc
400 V Class: 600 to 730 Vdc
Carrier Frequency
Depends on the converter capacity
• 6 kHz 2A0005 to 2A0030, 4A0005 to 4A0060
• 4 kHz 2A0050 to 2A0130, 4A0100 to 4A0185
• 2 kHz 4A0270 to 4A0630
Main Control Functions
Torque Limit, Cooling fan on/off switch, Removable Terminal Block with Parameter
Backup Function, MEMOBUS/Modbus Communication (RS-422/RS-485 max, 115.2 kbps)
Protection
Functions
Momentary Overcurrent
Protection
Operation stops when input current exceeds 200%.
Open Fuse
Operation stops if the fuse opens.
Overload
Operation stops after 60 s at 150% of rated output current.
Operation stops after 3 s at 200% of rated output current.
(power supply and regeneration)
Overvoltage Protection
(Output)
200 V class: Stops when DC bus voltage exceeds approximately 410 Vdc
400 V class: Stops when DC bus voltage exceeds approximately 820 Vdc
Overvoltage Protection
(Input)
200 V class: Stops when input voltage exceeds approximately 227 Vac
400 V class: Stops when input voltage exceeds approximately 554 Vac
Undervoltage Protection
(Output)
200 V class: Stops when DC bus voltage is approximately 190 Vdc
400 V class: Stops when DC bus voltage is approximately 380 Vdc
Undervoltage Protection
(Input)
200 V class: Stops when input voltage is approximately 150 Vac
400 V class: Stops when input voltage is approximately 300 Vac
Momentary Power Loss
Ride-Thru
Immediate stop after Momentary Power Loss is detected.
Power Supply Frequency
Fault
Operation stops if the input frequency deviates by
±6 Hz of rated frequency.
Heatsink Overheat
Protection
Thermistor protection
Ground Protection
Electronic circuit protection
DC Bus Charge LED
Remains lit until DC bus voltage is 50 V
Environment
Area of Use
Indoors
Ambient Temperature
IP00/Open Type enclosure: -10
°C to +50°C (14°F to 122°F)
IP20/Open Type enclosure: -10
°C to +40°C (14°F to 104°F)
Humidity
95 RH% or less (no condensation)
Vibration/Shock
10 to 20 Hz at 9.8 m/s
2
, 20 to 55 Hz at 5.9 m/s
2
(2A0005 to 2A0050, 4A0005 to 4A0100)
10 to 20 Hz at 9.8 m/s
2
20 to 55 Hz at 2.0 m/s
2
(2A0065 to 2A0130, 4A0130 to 4A0370)
10 to 20 Hz at 5.9 m/s
2
, 20 to 55 Hz at 2.0 m/s
2
(4A0630)
Storage Temperature
-20
°C to +60°C (-4°F to +140°F)
Altitude
1000 m (3281 ft) or lower, up to 3000 m (9843 ft) with derating.
Protection Design
IP00/Open Type enclosure, IP20/Open Type enclosure