5.4 Alarm Detection

124

YASKAWA ELECTRIC TOEP C710656 07C YASKAWA Power Regenerative Converter - D1000 Instruction Manual

The phase rotation direction has changed in the
input power supply.

Correct the wiring.

The detected power supply frequency exceeded
the allowable value.

Improve the power supply.

Digital Operator

Display

Minor Fault Name

Detail

Alarm

Output

(H2-=10)

HCA

Current Alarm

Converter current exceeded overcurrent warning level (150% of the rated
current).

YES

Cause

Possible Solutions

Load is too heavy.

Reduce the load for applications with repetitive operations (i.e., stops and starts), or replace the
converter.

Digital Operator

Display

Minor Fault Name

Detail

Alarm

Output

(H2-=10)

LT-1

Cooling Fan

Maintenance Time

The cooling fan has reached its expected maintenance period and may need to be
replaced.
Note: An alarm output (H2- = 10) will only be triggered if both (H2- =
2F and H2- = 10) are set.

YES

Cause

Possible Solutions

The cooling fan has reached 90% of its
expected performance life.

Replace the cooling fan and set o4-03 to 0 to reset the Maintenance Monitor.

Digital Operator

Display

Minor Fault Name

Detail

Alarm

Output

(H2-=10)

LT-2

Capacitor Maintenance

Time

The main circuit and control circuit capacitors are nearing the end of their
expected performance life.
Note: An alarm output (H2- = 10) will only be triggered if H2- = 2F.

YES

Cause

Possible Solutions

The main circuit and control circuit capacitors
have reached 90% of their expected
performance lives.

Replace either the control board or the entire converter. For instructions on replacing the control
board, contact Yaskawa or your nearest sales representative.

Digital Operator

Display

Minor Fault Name

Detail

Alarm

Output

(H2-=10)

LT-3

Soft Charge Bypass

Relay Maintenance

Time

The DC bus soft charge relay is nearing the end of its expected performance life.
Note: An alarm output (H2- = 10) will only be triggered if H2- = 2F.

YES

Cause

Possible Solutions

The DC bus soft charge relay has reached 90%
of expected performance life.

Replace either the control board or the entire converter. For instructions on replacing the control
board, contact Yaskawa or your nearest sales representative.

Digital Operator

Display

Minor Fault Name

Detail

Alarm

Output

(H2-=10)

oH

Heatsink Overheat

The temperature of the heatsink exceeded the overheat pre-alarm level set to
L8-02 (90-100

°C). Default value for L8-02 is determined by o2-04 (drive model

selection).

YES

Cause

Possible Solutions

Surrounding temperature is too high

• Check the surrounding temperature.
• Improve the air circulation within the enclosure panel.
• Install a fan or air conditioner to cool surrounding area.
• Remove anything near converter that may cause extra heat.

Airflow around the converter is restricted.

• Provide proper installation space around the converter as indicated in the manual. Refer to

Installation Orientation and Spacing on page 30

for details.

• Allow for the proper space and ensure that there is sufficient circulation around the control

panel.

• Check for dust or other foreign materials clogging the cooling fan.
• Clear debris caught in the fan that restricts air circulation.