5.4 Alarm Detection
122
YASKAWA ELECTRIC TOEP C710656 07C YASKAWA Power Regenerative Converter - D1000 Instruction Manual
Incompatible PLC software settings or there is
a hardware problem.
• Check the PLC.
• Remove the cause of the error on the controller side.
Communications cable is disconnected or
damaged.
• Check the connector to make sure the cable has a signal.
• Replace the communications cable.
Digital Operator
Display
Minor Fault Name
Detail
Alarm
Output
(H2-=10)
CoF
Current Offset Fault
A fault occurred in adjustment of the automatic current offset when the power
supply was turned on.
YES
Cause
Possible Solutions
A fault occurred in the current detection circuit.
Cycle the power supply and check operation.
• If the fault occurs again, replace the board or converter. For information on board replacement,
consult with your Yaskawa representative or the nearest Yaskawa sales office.
Digital Operator
Display
Minor Fault Name
Detail
Alarm
Output
(H2-=10)
CrST
Cannot Reset
A fault reset command was entered while the Run command was still present.
YES
Cause
Possible Solutions
Fault reset was being executed when a Run
command was entered.
• Ensure that a Run command cannot be entered from the external terminals or option during
fault reset.
• Turn off the Run command.
Digital Operator
Display
Minor Fault Name
Detail
Alarm
Output
(H2-=10)
CyC
MECHATROLINK
Communications Cycle
Setting Error
The MECHATROLINK option card is not set correctly.
YES
Cause
Possible Solutions
The communications cycle of the
MECHATROLINK option card is out of range.
Correct the setting.
Digital Operator
Display
Minor Fault Name
Detail
Alarm
Output
(H2-=10)
E5
MECHATROLINK
Watchdog Timer Error
A Watchdog Timer Error was detected.
YES
Cause
Possible Solutions
There is no continuity in the watchdog timer in
the data that is sent by the host controller.
Execute the DISCONNECT or ALM_CLR command, and then move to phase 3 again with the
CONNECT or SYNC_SET command.
Digital Operator
Display
Minor Fault Name
Detail
Alarm
Output
(H2-=10)
EF0
Option Card External
Fault
An external fault condition is present.
YES
Cause
Possible Solutions
An external fault was received from the PLC
with F6-03 set to 3, which allows the converter
to continue running after an external fault
occurs.
• Remove the cause of the external fault.
• Remove the external fault input from the PLC.
There is a problem with the PLC program.
Check the PLC program and correct problems.
TOEP_C710656_07C_2_0.book 122 ページ 2015年1月9日 金曜日 午後6時23分