3 Electrical Installation
YASKAWA ELECTRIC TOEP C710616 38F YASKAWA AC Drive L1000A Quick Start Guide
41
El
ec
tr
ical
I
n
st
al
lat
io
n
3
Note: When connecting peripheral devices and options to the terminals –, +1, +3, B1, and B2, refer to the instruction manuals for each
device. For more information, contact Yaskawa or your nearest sales representative.
4A0260
R/L1, S/L2, T/L3
3/0
× 2P
2/0 to 600
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3
3/0
× 2P
2/0 to 600
–, +1
–
3/0 to 600
+3
–
1 to 325
M10
18 to 23
(159 to 204)
2
2 to 350
M12
32 to 40
(283 to 354)
4A0304
R/L1, S/L2, T/L3
4/0
× 2P
3/0 to 600
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3
4/0
× 2P
3/0 to 600
–, +1
–
4/0 to 600
+3
–
3/0 to 600
M10
18 to 23
(159 to 204)
1
1 to 350
M12
32 to 40
(283 to 354)
4A0370
R/L1, S/L2, T/L3
300
× 2P
4/0 to 300
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3
300
× 2P
4/0 to 300
–, +1
–
3/0 to 300
+3
–
3/0 to 300
1
1 to 3/0
4A0450
R/L1, S/L2, T/L3
3/0
× 4P
3/0 to 300
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3
3/0
× 4P
3/0 to 300
–, +1
–
1/0 to 300
+3
–
1/0 to 300
1/0
1/0 to 300
4A0605
R/L1, S/L2, T/L3
300
× 4P
4/0 to 300
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3
300
× 4P
4/0 to 300
–, +1
–
1/0 to 300
+3
–
1/0 to 300
2/0
2/0 to 300
<1> When using the wire of this gauge in accordance with IEC/EN 61800-5-1, install an ELCB.
<2> When using the wire of this gauge in accordance with IEC/EN 61800-5-1, install an ELCB, or use copper wire of 10 mm
2
(AWG 8).
Model
CIMR-LU
Terminal
Recomm. Gauge
AWG, kcmil
Wire Range
AWG, kcmil
Screw
Size
Tightening Torque
N m (lb.in.)
TOEP_C710616_38F_5_0.book 41 ページ 2013年12月4日 水曜日 午前9時56分