Three-Phase 200 V Class Drives

Table 55 Power Ratings (Three-Phase 200 V Class)

Item

<1> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater than

the motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.

<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring

connections, and power supply impedance.

<3> DC is not available for UL standards.

<4> Rated motor capacity is calculated with a rated output voltage of 220 V.

<5> Carrier frequency can be set up to 8 kHz while keeping this current rating. Higher carrier frequency settings require derating.

<6> Carrier frequency can be set up to 5 kHz while keeping this current rating. Higher carrier frequency settings require derating.

Specification

CIMR-LU2A

0008 0011 0014 0018 0025 0033 0047 0060 0075 0085 0115 0145 0180 0215 0283 0346 0415

Maximum Applicable Motor Capacity

(HP)

<1>

2

3

4

3.7

(5)

7.5

10

15

20

25

30

40

50

60

75

100 125 150

Input

Input Current (A)

<2>

7.5

11

15.6 18.9

28

37

52

68

80

82

111 136 164 200 271 324 394

Rated Voltage

Rated Frequency

Three-phase 200 to 240 Vac 50/60 Hz/270 to 340 Vdc

<3>

Allowable Voltage

Fluctuation

-15 to 10%

Allowable Frequency

Fluctuation

±5%

Input Power (kVA)

4.1

5.8

7.8

9.5 14 18 27 36 44 37 51 62 75 91

124 148 180

Output

Rated Output Capacity

(kVA)

<4>

3

<5>

4.2

<5>

5.3

<5>

6.7

<5>

9.5

<5>

12.6

<5>

17.9

<5>

23

<5>

29

<5>

32

<5>

44

<5>

55

<6>

69

<6>

82

<6>

108

<6>

132

<6>

158

<6>

Rated Output Current (A)

8

<5>

11

<5>

14

<5>

17.5

<5>

25

<5>

33

<5>

47

<5>

60

<5>

75

<5>

85

<5>

115

<5>

145

<6>

180

<6>

215

<6>

283

<6>

346

<6>

415

<6>

Overload Tolerance

150% of rated output current for 60 s

Carrier Frequency

User adjustable between 2 and 15 kHz

User adjustable between 2 and

10 kHz

Maximum Output Voltage

(V)

Three-phase 200 to 240 V (proportional to input voltage)

Maximum Output Speed (Hz)

200 Hz (user-set)