H2: multi-function digital outputs – Yaskawa CIMR-LU Drives User Manual
Page 184
B Parameter Table
184
YASKAWA ELECTRIC TOEP C710616 38F YASKAWA AC Drive L1000A Quick Start Guide
■
H2: Multi-Function Digital Outputs
No.
Name
Description
Setting
H2-01
Terminals M1-M2
Function Selection (relay)
H2 Multi-Function Digital Output Settings on page 184
for a description of
setting values.
Default: 50
Min: 0
Max: 161
H2-02
Terminals M3-M4
Function Selection (relay)
Default: 51
Min: 0
Max: 161
H2-03
Terminals M5-M6
Function Selection (relay)
Default: 6
Min: 0
Max: 161
H2-04
Terminal P1-C1 Function
Selection (photocoupler)
Default: 37
Min: 0
Max: 161
H2-05
Terminal P2-C2 Function
Selection (photocoupler)
Default: F
Min: 0
Max: 161
H2 Multi-Function Digital Output Settings
H2-
Setting
Function
Description
0
During Run
Closed: An Up/Down command is active or voltage is output.
1
Zero Speed
Open: Output speed is greater than the value of E1-09 (Minimum Output Frequency) or S1-01 (Zero
Speed Level at Stop).
Closed: Output frequency is less than or equal to the value of E1-09 (Minimum Output Frequency) or
S1-01 (Zero Speed Level at Stop).
2
Speed Agree 1
Closed: Output speed equals the speed reference (plus or minus the hysteresis set to L4-02).
3
User-set Speed Agree 1
Closed: Output speed and speed reference equal L4-01 (plus or minus the hysteresis set to L4-02).
4
Speed Detection 1
Closed: Output speed is less than or equal to the value in L4-01 with hysteresis determined by L4-02.
5
Speed Detection 2
Closed: Output speed is greater than or equal to the value in L4-01 with hysteresis determined by L4-02.
6
Drive Ready (READY)
Closed: Power up is complete and the drive is ready to accept an Up/Down command.
7
DC Bus Undervoltage
Closed: DC bus voltage is below the Uv trip level set in L2-05.
8
During Baseblock (N.O.)
Closed: Drive has entered the baseblock state (no output voltage).
9
Speed Reference Source
Open: The speed reference is supplied by an external reference (set in b1-01).
Closed: Digital operator supplies the speed reference.
A
Up/Down Command Source
Open: The Up/Down command is supplied by an external reference (set in b1-02).
Closed: Digital operator supplies the Up/Down command.
B
Torque Detection 1
Closed: An overtorque or undertorque situation has been detected.
E
Fault
Closed: Fault occurred. (excluding CPF00 and CPF01)
F
Not used (Through Mode)
Set this value when the terminal is not used or when using the terminal in the pass-through mode.
10
Minor Fault
Closed: An alarm has been triggered, or the IGBTs have reached 90% of their expected life span.
11
Fault Reset Command
Active
Closed: The drive has received a reset command from the multi-function input terminals or from serial
network, or the digital operator’s RESET key has been pressed.
12
Timer Output
Closed: Timer output.
13
Speed Agree 2
Closed: When drive output frequency equals the speed reference ±L4-04.
14
User-set Speed Agree 2
Closed: When the drive output speed is equal to the value in L4-03 ±L4-04.
15
Speed Detection 3
Closed: When the drive output speed is less than or equal to the value in L4-03 ±L4-04.
16
Speed Detection 4
Closed: When the output speed is greater than or equal to the value in L4-03 ±L4-04.
18
Torque Detection 2
Closed: Overtorque or undertorque has been detected.
1A
During Down Direction
Closed: Drive is running in the down direction.
1B
During Baseblock 2 (N.C.)
Open: Drive has entered the baseblock state (no output voltage).