Yaskawa CIMR-LU Drives User Manual
Page 37
![background image](https://www.manualsdir.com/files/819676/content/doc037.png)
3 Electrical Installation
YASKAWA ELECTRIC TOEP C710616 38F YASKAWA AC Drive L1000A Quick Start Guide
37
El
ec
tr
ical
I
n
st
al
lat
io
n
3
Three-Phase 200 V Class
Table 10 Wire Gauge and Torque Specifications (Three-Phase 200 V Class)
Model
CIMR-LU
Terminal
Recomm. Gauge
AWG, kcmil
Wire Range
AWG, kcmil
Screw
Size
Tightening Torque
N m (lb.in.)
2A0008
R/L1, S/L2, T/L3
14
14 to 10
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/T3
14
14 to 10
–, +1, +2
–
14 to 10
B1, B2
–
14 to 10
14 to 10
2A0011
R/L1, S/L2, T/L3
12
14 to 10
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/T3
14
14 to 10
–, +1, +2
–
14 to 10
B1, B2
–
14 to 10
14 to 10
2A0014
R/L1, S/L2, T/L3
10
12 to 10
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/T3
10
14 to 10
–, +1, +2
–
14 to 10
B1, B2
–
14 to 10
14 to 10
2A0018
R/L1, S/L2, T/L3
10
18 to 10
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/T3
10
18 to 10
–, +1, +2
–
12 to 10
B1, B2
–
14 to 10
12 to 10
2A0025
R/L1, S/L2, T/L3
8
12 to 6
M4
2.1 to 2.3
(18.6 to 20.4)
U/T1, V/T2, W/T3
8
12 to 6
–, +1, +2
–
10 to 6
B1, B2
–
12 to 10
10 to 8
M5
2.0 to 2.5
(17.7 to 22.1)
2A0033
R/L1, S/L2, T/L3
6
12 to 6
M4
2.1 to 2.3
(18.6 to 20.4)
U/T1, V/T2, W/T3
8
12 to 6
–, +1, +2
–
6
B1, B2
–
12 to 10
8
10 to 8
M5
2.0 to 2.5
(17.7 to 22.1)
2A0047
R/L1, S/L2, T/L3
4
6 to 4
M6
5.4 to 6.0
(47.8 to 53.1)
U/T1, V/T2, W/T3
4
6 to 4
–, +1, +2
–
6 to 4
B1, B2
–
10 to 6
M5
2.7 to 3.0
(23.9 to 26.6)
6
8 to 6
M6
5.4 to 6.0
(47.8 to 53.1)
2A0060
R/L1, S/L2, T/L3
3
10 to 2
M8
9.9 to 11.0
(87.6 to 97.4)
U/T1, V/T2, W/T3
3
10 to 2
–, +1, +2
–
4 to 3
B1, B2
–
8 to 6
M5
2.7 to 3.0
(23.9 to 26.6)
6
6 to 4
M6
5.4 to 6.0
(47.8 to 53.1)
TOEP_C710616_38F_5_0.book 37 ページ 2013年12月4日 水曜日 午前9時56分