Periodic maintenance, Replacement parts – Yaskawa CIMR-LU Drives User Manual
Page 143
6 Periodic Inspection & Maintenance
YASKAWA ELECTRIC TOEP C710616 38F YASKAWA AC Drive L1000A Quick Start Guide
143
Pe
ri
odic
Inspe
c
ti
on &
Maint
ena
nc
e
6
◆ Periodic Maintenance
The drive has Maintenance Monitors that keep track of component wear. This feature provides advance maintenance
warning and eliminates the need to shut down the entire system for unexpected problems. The drive allows the user to
check predicted maintenance periods for the components listed below.
• Cooling Fan, Circulation Fan, Control Board Cooling Fan
• Electrolytic Capacitors
• Inrush Prevention Circuit
• IGBTs
For replacement parts, contact the distributor where the drive was purchased or contact Yaskawa directly.
■
Replacement Parts
contains the estimated performance life of components that require replacement during the life of the drive. Only
use Yaskawa replacement parts for the appropriate drive model and revision.
Table 42 Estimated Performance Life
NOTICE: Estimated performance life based on specific usage conditions. These conditions are provided for the purpose of replacing
parts to maintain performance. Some parts may require more frequent replacement due to poor environments or rigorous use. Usage
conditions for estimated performance life:
Ambient temperature: Yearly average of 40
°C (104°F) (IP00 enclosure)
Load factor: 80% maximum
Operation time: 24 hours a day
Circuit Boards
Check for any odor, discoloration, and rust. Make
sure connections are properly fastened and that no
dust or oil mist has accumulated on the surface of the
board.
• Fix any loose connections.
• If an antistatic cloth or vacuum plunger cannot
be used, replace the board.
• Do not use any solvents to clean the board.
• Remove foreign particles and dust by sucking
them out with a vacuum cleaner to avoid
touching parts.
• The drive has few serviceable parts and may
require complete drive replacement.
Cooling System Periodic Inspection
Cooling Fan,
Circulation Fan,
Control Board
Cooling Fan
• Check for abnormal oscillation or unusual noise.
• Check for damaged or missing fan blades.
• Clean or replace the fan.
Heatsink
Inspect for dust or other foreign material collected on
the surface.
Remove foreign particles and dust by sucking
them out with a vacuum cleaner to avoid touching
parts.
Air Duct
Inspect air intake and exhaust openings. They must
be free from obstruction and properly installed.
• Visually inspect the area.
• Clear obstructions and clean air duct as
required.
Display Periodic Inspection
Digital Operator
• Make sure data appears on the operator properly.
• Inspect for dust or other foreign material that may
have collected on surrounding components.
• Contact a Yaskawa representative if there is any
trouble with the display or keypad.
• Clean the digital operator.
Component
Estimated Performance Life
Cooling Fan, Circulation Fan
<1> The drive has few serviceable parts and may require complete drive replacement.
10 years
Electrolytic Capacitors
10 years
Inspection Area
Inspection Points
Corrective Action
Checked
TOEP_C710616_38F_5_0.book 143 ページ 2013年12月4日 水曜日 午前9時56分