3 Electrical Installation
40
YASKAWA ELECTRIC TOEP C710616 38F YASKAWA AC Drive L1000A Quick Start Guide
4A0039
R/L1, S/L2, T/L3
6
6 to 4
M6
5.4 to 6.0
(47.8 to 53.1)
U/T1, V/T2, W/T3
6
6 to 4
–, +1, +2
–
6 to 4
B1, B2
–
10 to 8
M5
2.7 to 3.0
(23.9 to 26.6)
6
8 to 6
M6
5.4 to 6.0
(47.8 to 53.1)
4A0045
R/L1, S/L2, T/L3
4
10 to 1/0
M8
9 to 11
(79.7 to 97.4)
U/T1, V/T2, W/T3
4
10 to 1/0
–, +1
–
6 to 1
B1, B2
–
8 to 4
6
8 to 6
4A0060
R/L1, S/L2, T/L3
3
10 to 3/0
M8
9 to 11
(79.7 to 97.4)
U/T1, V/T2, W/T3
3
10 to 3/0
–, +1
–
4 to 1
B1, B2
–
6 to 3
6
6
4A0075
R/L1, S/L2, T/L3
2
6 to 250
M8
9 to 11
(79.7 to 97.4)
U/T1, V/T2, W/T3
2
6 to 250
–, +1
–
3 to 1/0
+3
–
6 to 1/0
4
6 to 4
4A0091
R/L1, S/L2, T/L3
1/0
6 to 250
M8
9 to 11
(79.7 to 97.4)
U/T1, V/T2, W/T3
1
6 to 250
–, +1
–
3 to 1/0
+3
–
4 to 1/0
4
6 to 4
4A0112
R/L1, S/L2, T/L3
3/0
1/0 to 4/0
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3
2/0
1/0 to 4/0
–, +1
–
1/0 to 4/0
+3
–
3 to 4/0
4
4
4A0150
R/L1, S/L2, T/L3
4/0
1/0 to 4/0
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3
4/0
1/0 to 4/0
–, +1
–
1 to 4/0
+3
–
1/0 to 4/0
4
4 to 2
4A0180
R/L1, S/L2, T/L3
1
× 2P
2 to 300
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3
1
× 2P
2 to 300
–, +1
–
1 to 250
+3
–
3 to 3/0
4
4 to 300
4A0216
R/L1, S/L2, T/L3
2/0
× 2P
1 to 600
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3
2/0
× 2P
1/0 to 600
–, +1
–
3/0 to 600
+3
–
1 to 325
2
2 to 350
Model
CIMR-LU
Terminal
Recomm. Gauge
AWG, kcmil
Wire Range
AWG, kcmil
Screw
Size
Tightening Torque
N m (lb.in.)
TOEP_C710616_38F_5_0.book 40 ページ 2013年12月4日 水曜日 午前9時56分