Yaskawa CIMR-LU Drives User Manual
Page 38
3 Electrical Installation
38
YASKAWA ELECTRIC TOEP C710616 38F YASKAWA AC Drive L1000A Quick Start Guide
2A0075
R/L1, S/L2, T/L3
2
10 to 2
M8
9.9 to 11.0
(87.6to 97.4)
U/T1, V/T2, W/T3
2
10 to 2
–, +1, +2
–
3 to 2
B1, B2
–
6
M5
2.7 to 3.0
(23.9 to 26.6)
6
6 to 4
M6
5.4 to 6.0
(47.8 to 53.1)
2A0085
R/L1, S/L2, T/L3
1/0
10 to 1/0
M8
9 to 11
(79.7 to 97.4)
U/T1, V/T2, W/T3
1/0
10 to 1/0
–, +1
–
2 to 1/0
B1, B2
–
6 to 1/0
6
6 to 4
2A0115
R/L1, S/L2, T/L3
2/0
10 to 3/0
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3
2/0
10 to 3/0
–, +1
–
1/0 to 3/0
B1, B2
–
4 to 2/0
4
4
M8
9 to 11
(79.7 to 97.4)
2A0145
R/L1, S/L2, T/L3
4/0
1/0 to 4/0
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3
4/0
1/0 to 4/0
–, +1
–
1 to 4/0
+3
–
1/0 to 4/0
4
4 to 2
9 to 11
(79.7 to 97.4)
2A0180
R/L1, S/L2, T/L3
1/0
× 2P
1/0 to 4/0
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3
1/0
× 2P
1/0 to 4/0
–, +1
–
1 to 4/0
+3
–
1/0 to 4/0
4
4 to 1/0
9 to 11
(79.7 to 97.4)
2A0215
R/L1, S/L2, T/L3
2/0
× 2P
3/0 to 300
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3
2/0
× 2P
3/0 to 300
–, +1
–
3/0 to 300
+3
–
2 to 300
M10
18 to 23
(159 to 204)
3
3 to 300
M12
32 to 40
(283 to 354)
2A0283
R/L1, S/L2, T/L3
3/0
× 2P
3/0 to 300
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3
3/0
× 2P
3/0 to 300
–, +1
–
3/0 to 300
+3
–
3/0 to 300
M10
18 to 23
(159 to 204)
2
2 to 300
M12
32 to 40
(283 to 354)
2A0346
R/L1, S/L2, T/L3
250
× 2P
4/0 to 600
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3
4/0
× 2P
4/0 to 600
–, +1
–
250 to 600
+3
–
3/0 to 600
M10
18 to 23
(159 to 204)
1
1 to 350
M12
32 to 40
(283 to 354)
Model
CIMR-LU
Terminal
Recomm. Gauge
AWG, kcmil
Wire Range
AWG, kcmil
Screw
Size
Tightening Torque
N m (lb.in.)
TOEP_C710616_38F_5_0.book 38 ページ 2013年12月4日 水曜日 午前9時56分