Table 63 – Yaskawa CIMR-LU Drives User Manual
Page 226
C Standards Compliance
226
YASKAWA ELECTRIC TOEP C710616 38F YASKAWA AC Drive L1000A Quick Start Guide
Table 63 Wire Gauge and Torque Specifications (Three-Phase 400 V Class)
Model
CIMR-LU
Terminal
Recommended
Gauge
AWG, kcmil
Applicable Gauge
AWG, kcmil
Screw
Size
Tightening Torque
N m (lb.in.)
4A0005
4A0006
4A0007
R/L1, S/L2, T/L3
14
14 to 10
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/T3
14
14 to 10
–, +1, +2
–
14 to 10
B1, B2
–
14 to 10
10
14 to 10
4A0009
R/L1, S/L2, T/L3
12
14 to 10
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/T3
14
14 to 10
–, +1, +2
–
14 to 10
B1, B2
–
14 to 10
10
14 to 10
4A0015
R/L1, S/L2, T/L3
10
12 to 6
M4
2.1 to 2.3
(18.6 to 20.4)
U/T1, V/T2, W/T3
10
12 to 6
–, +1, +2
–
12 to 6
B1, B2
–
12 to 10
10
14 to 10
M5
2.0 to 2.5
(17.7 to 22.1)
4A0018
R/L1, S/L2, T/L3
10
10 to 6
M4
2.1 to 2.3
(18.6 to 20.4)
U/T1, V/T2, W/T3
10
10 to 6
–, +1, +2
–
12 to 6
B1, B2
–
12 to 10
10
12 to 10
M5
2.0 to 2.5
(17.7 to 22.1)
4A0024
R/L1, S/L2, T/L3
8
8 to 6
M5
3.6 to 4.0
(31.8 to 35.4)
U/T1, V/T2, W/T3
8
10 to 6
–, +1, +2
–
10 to 6
B1, B2
–
10 to 8
M5
2.7 to 3.0
(23.9 to 26.6)
8
10 to 8
M6
5.4 to 6.0
(47.8 to 53.1)
4A0031
R/L1, S/L2, T/L3
6
8 to 6
M5
3.6 to 4.0
(31.8 to 35.4)
U/T1, V/T2, W/T3
8
8 to 6
–, +1, +2
–
6
B1, B2
–
10 to 8
M5
2.7 to 3.0
(23.9 to 26.6)
6
10 to 6
M6
5.4 to 6.0
(47.8 to 53.1)
4A0039
R/L1, S/L2, T/L3
6
6 to 4
M6
5.4 to 6.0
(47.8 to 53.1)
U/T1, V/T2, W/T3
6
6 to 4
–, +1, +2
–
6 to 4
B1, B2
–
10 to 8
M5
2.7 to 3.0
(23.9 to 26.6)
6
8 to 6
M6
5.4 to 6.0
(47.8 to 53.1)
4A0045
R/L1, S/L2, T/L3
4
6 to 4
M8
9 to 11
(79.7 to 97.4)
U/T1, V/T2, W/T3
4
6 to 4
–, +1
–
6 to 1
B1, B2
–
8 to 4
6
8 to 6
TOEP_C710616_38F_5_0.book 226 ページ 2013年12月4日 水曜日 午前9時56分