EMC Guidelines Compliance
This drive is tested according to European standards IEC/EN 61800-3: 2004, and complies with the European standards
IEC/EN 12015 (requires an optional AC reactor) and IEC/EN 12016.
Note: Make sure the protective earthing conductor complies with technical standards and local safety regulations. Because the leakage
current exceeds 3.5 mA when an EMC filter is installed, IEC/EN 61800-5-1 states that either the power supply must be
automatically disconnected in case of discontinuity of the protective earthing conductor or a protective earthing conductor with a
cross-section of at least 10 mm
2
(Cu) or 16 mm
2
(Al) must be used.
EMC Filter Installation
The following conditions must be met to ensure continued compliance with European standards IEC/EN 12015 and IEC/
EN 12016.
Refer to EMC Filters on page 221
for EMC filter selection.
Installation Method
Verify the following installation conditions to ensure that other devices and machinery used in combination with this
drive also comply with EMC guidelines.
1.
Install an EMC noise filter to the input side specified by Yaskawa for compliance with European standards.
2.
Place the drive and EMC noise filter in the same enclosure.
3.
Use braided shield cable for the drive and motor wiring, or run the wiring through a metal conduit.
4.
Keep wiring as short as possible. Ground the shield on both the drive side and the motor side.
Figure 94
Figure 103 Installation Method
5.
Make sure the ground conductor complies with technical standards and local safety rules. When an EMC filter is
installed, the leakage current exceeds 3.5 mA. Therefore according to IEC/EN 61800-5-1, at least one of the
conditions below must be satisfied:
a) The cross-section of the protective earthing conductor must be at least 10 mm
2
(Cu) or 16 mm
2
(Al).
b) The power supply must be disconnected automatically in case of discontinuity of the protective earthing
conductor.
Figure 95
Figure 104 Ground Area
6.
Connect an AC reactor or a DC link choke to minimize harmonic distortion.
A – Drive
D – Metal conduit
B – 10 m max cable length between drive and motor
E – Ground wire should be as short as possible.
C – Motor
A – Braided shield cable