beautypg.com

Yea_common – Yaskawa CIMR-LU Drives User Manual

Page 114

background image

4 Start-Up Programming & Operation

114

YASKAWA ELECTRIC TOEP C710616 38F YASKAWA AC Drive L1000A Quick Start Guide

Refer to the following table to install the inrush current suppression circuit for battery.

Table 34 Installation of the Inrush Current Suppression Circuit for Battery

Voltage

<1> Select the appropriate relay referring to the following calculation even if the battery voltage or main power current is applied.

Drive Model

CIMR-LU

Resistor

Relay

200 V

2A0215

1.0

Ω, 80 W

<1>

2A0283

1.0

Ω, 80 W

2A0346

1.0

Ω, 80 W

2A0415

1.0

Ω, 80 W

400 V

4A0150

1.0

Ω, 120 W

4A0180

1.0

Ω, 220 W

4A0216

1.0

Ω, 220 W

4A0260

1.0

Ω, 220 W

4A0304

1.0

Ω, 220 W

4A0370

1.0

Ω, 500 W

4A0450

2.0

Ω, 1000 W

4A0605

2.0

Ω, 1000 W

575V

5A0099

2.0

Ω, 220 W

5A0130

2.0

Ω, 220 W

5A0172

2.0

Ω, 440 W

5A0200

2.0

Ω, 440 W

Load current of battery (A) =

Motor rated power (kW)

× Operation frequency when running battery (Hz) × 2 × 1000

Battery voltage (Vdc)

× 0.6 (Motor efficiency) × Motor rated frequency (Hz)

YEA_common

TOEP_C710616_38F_5_0.book 114 ページ 2013年12月4日 水曜日 午前9時56分