4 Start-Up Programming & Operation

116

YASKAWA ELECTRIC TOEP C710616 38F YASKAWA AC Drive L1000A Quick Start Guide

Using a Battery for the DC Bus and 24 V Power Supply Unit Option for the Control Circuit

Follow the instructions when using a 24 V Power Supply Unit option for the control circuit and a battery for the main
circuit. The main circuit battery voltage must be higher than 48 Vdc for 200 V, 400 V, and 600 V class drives.

Yaskawa offers a 24 V Power Supply Option for the control circuit that is useful in applications unable to connect to a
backup battery greater than 250 V. Wiring instructions can be found in

Figure 57

to

Figure 59

. For a more detailed

explanation of the 24 V Power Supply Option, refer to the manual provided with the option.

Wiring for CIMR-LU2A0008 to 2A0180, 4A0005 to 4A0112, and 5A0003 to 5A0077

Figure 50

Figure 57 Using a Battery for the DC Bus and 24 V Power Supply Unit Option for the Control Circuit

Operation Sequence

Starting Rescued Operation

1.

Open contactor B and wait at least 5 seconds.

2.

Set the input terminal programmed for Rescue Operation (H1-

= 55).

3.

Close contactors A and C.

4.

Set the Up/Down command.

Ending Rescue Operation

1.

After the car has stopped, open contactors A and C.

2.

Clear the input terminal set for Rescue Operation (H1-

= 55).

3.

Wait at least 0.5 s and then close contactor B to return to operation with normal power supply.

-

CN19

1

4

W/T3

V/T2

U/T1

R/L1

S/L2

T/L3

B1

+2

+1

B2

SC

S

3

to S

8

5 s

0.5 s

24 Vdc

L1

L2

L3

L1000A

Magnetic Contactor Sequence

Battery for DC bus

DC bus power supply

Battery for

control circuit

H1-

غغ = 55

(Rescue Operation)

200 V Class: 48 to 340 Vdc
400 V Class: 48 to 680 Vdc
600 V Class: 48 to 850 Vdc

Magnetic Contactor A

Magnetic Contactor B

Magnetic Contactor C

Control

circuit

Power supply

24 V

Power
Supply

Unit

H1-

غغ = 55

(Rescue Operation)

Magnetic Contactor B

Magnetic Contactor A

Magnetic Contactor C

YEA_common