Three-phase 400 v class drives, Table 56, A specifications – Yaskawa CIMR-LU Drives User Manual
Page 160

A Specifications
160
YASKAWA ELECTRIC TOEP C710616 38F YASKAWA AC Drive L1000A Quick Start Guide
◆ Three-Phase 400 V Class Drives
Table 56 Power Ratings (Three-Phase 400 V Class)
Item
Specification
CIMR-LU4A
0005
0006
0007
0009
0015
0018
0024
0031
0039
0045
0060
Maximum Applicable Motor Capacity
2
3
5
7.5
10
15
20
25
25-30
25-30
40
Input
Input Current (A)
3.6
5.1
8.3
12
16
23
31
38
44
43
58
Rated Voltage
Rated Frequency
Three-phase 380 to 480 Vac 50/60 Hz 510 to 680 Vdc
Allowable Voltage
Fluctuation
-15 to 10%
Allowable Frequency
Fluctuation
±5%
Input Power (kVA)
4.1
5.8
9.5
14
18
26
35
43
46.6 39.3 53.0
Output
Rated Output Capacity
(kVA)
3.5
4.1
6.3
9.8
12
17
22
27
30
34
48
Rated Output Current
(A)
3.5
4.1
6.3
9.8
12
17
22
27
39
45
60
Overload Tolerance
150% of rated output current for 60 s
Carrier Frequency
User adjustable between 2 and 15 kHz
Maximum Output
Voltage (V)
Three-phase 380 to 480 V (proportional to input voltage)
Maximum Output Speed
(Hz)
200 Hz (user-adjustable)
Item
<1> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater
than the motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.
<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring
conditions, and power supply impedance.
<3> DC is not available for UL standards.
Specification
CIMR-LU4A
0075
0091
0112
0150
0180
0216
0260
0304
0370
0450
0605
Maximum Applicable Motor Capacity
50-60
50-60
75
100
125-150
150
200
250
300
350
400-
450-
500
Input
Input Current (A)
71
86
105
142
170
207
248
300
346
410
584
Rated Voltage
Rated Frequency
Three-phase 380 to 480 Vac 50/60 Hz 510 to 680 Vdc
Allowable Voltage
Fluctuation
-15 to 10%
Allowable Frequency
Fluctuation
±5%
Input Power (kVA)
64.9 78.6 96.0 129.9 155
189
227
274
316
375
534
Output
Rated Output Capacity
(kVA)
57
69
85
114
137
165
198
232
282
343
461
Rated Output Current
(A)
75
91
112
150
180
216
260
304
370
450
605
Overload Tolerance
150% of rated output current for 60 s
Carrier Frequency
User adjustable
between
2 and 15 kHz
User adjustable between 2 and 10 kHz
User-adjustable
between
2 and 5 kHz
Maximum Output
Voltage (V)
Three-phase 380 to 480 V (proportional to input voltage)
Maximum Output Speed
(Hz)
200 Hz (user-adjustable)
400 Hz (user-adjustable)
TOEP_C710616_38F_5_0.book 160 ページ 2013年12月4日 水曜日 午前9時56分