Yaskawa CIMR-LU Drives User Manual
Page 229

C Standards Compliance
YASKAWA ELECTRIC TOEP C710616 38F YASKAWA AC Drive L1000A Quick Start Guide
229
St
an
dar
d
s
Co
mplia
nce
C
5A0017
R/L1, S/L2, T/L3
8
10 to 6
M5
3.6 to 4.0
(31.8 to 35.4)
U/T1, V/T2, W/T3
10
10 to 6
–, +1, +2
–
10 to 6
B1, B2
–
10 to 8
2.7 to 3.0
(23.9 to 26.6)
8
10 to 8
M6
5.4 to 6.0
(47.8 to 53.1)
5A0022
5A0027
R/L1, S/L2, T/L3
6
6 to 4
M6
5.4 to 6.0
(47.8 to 53.1)
U/T1, V/T2, W/T3
6
6 to 4
–, +1, +2
–
6 to 4
B1, B2
–
10 to 8
M5
2.7 to 3.0
(23.9 to 26.6)
6
10 to 6
M6
5.4 to 6.0
(47.8 to 53.1)
5A0032
R/L1, S/L2, T/L3
6
10 to 3
M8
9 to 11
(79.7 to 97.4)
U/T1, V/T2, W/T3
6
10 to 3
–, +1
–
6 to 1
B1, B2
–
12 to 3
6
6
5A0041
R/L1, S/L2, T/L3
4
10 to 3
M8
9 to 11
(79.7 to 97.4)
U/T1, V/T2, W/T3
6
10 to 3
–, +1
–
6 to 1
B1, B2
–
8 to 3
6
6
5A0052
R/L1, S/L2, T/L3
4
10 to 4/0
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3
4
10 to 4/0
–, +1
–
4 to 4/0
+3
–
6 to 4/0
4
4
5A0062
R/L1, S/L2, T/L3
3
10 to 4/0
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3
3
10 to 4/0
–, +1
–
3 to 4/0
+3
–
6 to 4/0
4
4
5A0077
R/L1, S/L2, T/L3
1/0
10 to 4/0
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3
1
10 to 4/0
–, +1
–
2 to 4/0
+3
–
4 to 4/0
4
4
5A0099
R/L1, S/L2, T/L3
2/0
1 to 300
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3
2/0
1 to 300
–, +1
–
2/0 to 3/0
+3
–
1 to 1/0
3
4 to 300
5A0130
R/L1, S/L2, T/L3
3/0
2/0 to 300
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3
3/0
2/0 to 300
–, +1
–
3/0 to 4/0
+3
–
1/0 to 2/0
3
4 to 300
Model
CIMR-LU
Terminal
Recomm. Gauge
AWG, kcmil
Wire Range
AWG, kcmil
Screw
Size
Tightening Torque
N m (lb.in.)
TOEP_C710616_38F_5_0.book 229 ページ 2013年12月4日 水曜日 午前9時56分