beautypg.com

Figure 59, Yea_common, 4 start-up programming & operation – Yaskawa CIMR-LU Drives User Manual

Page 118

background image

4 Start-Up Programming & Operation

118

YASKAWA ELECTRIC TOEP C710616 38F YASKAWA AC Drive L1000A Quick Start Guide

• Voltage Lower Than 190 to 340 Vdc for 200 V Class Drives, 380 to 680 Vdc for 400 V Class Drives, and 500 to 850

Vdc for 600 V Class Drives

Figure 52

Figure 59 Voltage Lower Than 190 to 340 Vdc for 200 V Class Drives, 380 to 680 Vdc for 400 V Class Drives,

and 500 to 850 Vdc for 600 V Class Drives

+

Current

sensor

R/L1
S/L2
T/L3

+1

+3

U/T1
V/T2
W/T3

Relay

Power
supply

board

Control

board

OPE

(A)

(B)

DC bus
power supply

H1-

= 55

(Rescue Operation)

L1
L2
L3

DC bus power supply

200 V Class: 190 to 340 Vdc
400 V Class: 380 to 680 Vdc
600 V Class: 500 to 850 Vdc

L1000A

S

3

to S

12

SC

Magnetic Contactor Sequence

Magnetic Contactor B

Magnetic Contactor A

Magnetic Contactor C

H1-

= 55

(Rescue Operation)

After the DC bus voltage falls lower
than the battery voltage

0.5 s

24 Vdc

Battery for

control circuit

Magnetic Contactor C

24 V

Power
Supply

Unit

CN19

YEA_common

TOEP_C710616_38F_5_0.book 118 ページ 2013年12月4日 水曜日 午前9時56分