S6-10: overacceleration detection level, S6-11: overacceleration detection time, S6-12: overacceleration detection selection – Yaskawa CIMR-LU Drives User Manual
Page 107: S6-15: speed reference loss detection, S6-16: restart after baseblock selection
4 Start-Up Programming & Operation
YASKAWA ELECTRIC TOEP C710616 38F YASKAWA AC Drive L1000A Quick Start Guide
107
S
tart-U
p
Prog
rammin
g
&
Op
er
at
io
n
4
■
S6-10: Overacceleration Detection Level
If the elevator car accelerates at an abnormal rate, the drive triggers an overacceleration fault (dv6) and the motor coasts
to stop. Parameter S6-10 determines the acceleration rate that triggers the dv6 fault. A setting of 0.0 m/s
2
disables
overacceleration detection.
■
S6-11: Overacceleration Detection Time
Sets the time that the acceleration must exceed the overacceleration detection level before as fault is triggered.
■
S6-12: Overacceleration Detection Selection
Determines the conditions for detecting an overacceleration situation.
Setting 0: Always enabled
Setting 1: During run only
■
S6-15: Speed Reference Loss Detection
Enabled or disables detection for missing speed reference (FrL).
Setting 0: Disabled
Setting 1: Enabled
■
S6-16: Restart after Baseblock Selection
Allows the drive to restart the motor after returning to normal operation from Baseblock state (H1-
= 8/9) or from
Safe Torque-Off state (Safe Disable inputs H1 and H2 enabled) while the Up/Down command is still active.
Setting 0: No restart after Baseblock or Safe Torque-Off
Do not restart the motor when leaving the Baseblock or Safe Torque-Off state even if an Up/Down command is still
active.
Setting 1: Restart after Baseblock or Safe Torque-Off
Restart when the Up/Down command is still active while the Baseblock or Safe Torque-Off state is left. To use this
function with the Safe Disable function, parameter L8-88 must be set to 1.
No.
<1> Default setting is determined by parameter o1-03. If o1-03 is set to 0 through 5, the default is 1.5 m/s2. If o1-03 is set to 6, the default is 5.0 ft/
s
2
(setting range: 0.0 to 50.0 ft/s
2
).
Parameter Name
Setting Range
Default
S6-10
Overacceleration Detection Level
0.0 to 20.0 m/s
2
1.5 m/s
No.
Parameter Name
Setting Range
Default
S6-11
Overacceleration Detection Time
0 to 5000 ms
50 ms
No.
Parameter Name
Setting Range
Default
S6-12
Overacceleration Detection Selection
0 or 1
0
No.
Parameter Name
Setting Range
Default
S6-15
Speed Reference Loss Detection
0 or 1
1
No.
Parameter Name
Setting Range
Default
S6-16
Restart after Baseblock Selection
0 or 1
0
TOEP_C710616_38F_5_0.book 107 ページ 2013年12月4日 水曜日 午前9時56分