beautypg.com

F4: analog monitor card (ao-a3), F5: digital output card (do-a3) – Yaskawa CIMR-LU Drives User Manual

Page 180

background image

B Parameter Table

180

YASKAWA ELECTRIC TOEP C710616 38F YASKAWA AC Drive L1000A Quick Start Guide

F4: Analog Monitor Card (AO-A3)

F5: Digital Output Card (DO-A3)

No.

Name

Description

Setting

F4-01

Terminal V1 Function
Selection

Sets the monitor signal for output from terminal V1. Set this parameter to the last
three digits of the desired U -

monitor. Some U parameters are available only in

certain control modes.

Default: 102
Min: 000
Max: 999

F4-02

Terminal V1 Gain

Sets the gain for voltage output via terminal V1.

Default: 100.0%
Min: -999.9%
Max: 999.9%

F4-03

Terminal V2 Function
Selection

Sets the monitor signal for output from terminal V2. Set this parameter to the last
three digits of the desired U -

monitor. Some U parameters are available only in

certain control modes.

Default: 103
Min: 000
Max: 999

F4-04

Terminal V2 Gain

Sets the gain for voltage output via terminal V2.

Default: 50.0%
Min: -999.9%
Max: 999.9%

F4-05

Terminal V1 Bias

Sets the amount of bias added to the voltage output via terminal V1.

Default: 0.0%
Min: -999.9%
Max: 999.9%

F4-06

Terminal V2 Bias

Sets the amount of bias added to the voltage output via terminal V2.

Default: 0.0%
Min: -999.9%
Max: 999.9%

F4-07

Terminal V1 Signal Level
Selection

0: 0 to 10 V
1: -10 to 10 V

Default: 1
Min: 0
Max: 1

F4-08

Terminal V2 Signal Level
Selection

Default: 1
Min: 0
Max: 1

No.

Name

Description

Setting

F5-01

Terminal P1-C1 Output
Selection

Sets the function for contact output terminals M1-M2, M3-M4, and photocoupler
output terminals P1 through P6.

Default: 0
Min: 0
Max: 161

F5-02

Terminal P2-C2 Output
Selection

Default: 1
Min: 0
Max: 161

F5-03

Terminal P3-C3 Output
Selection

Default: 2
Min: 0
Max: 161

F5-04

Terminal P4-C4 Output
Selection

Default: 4
Min: 0
Max: 161

F5-05

Terminal P5-C5 Output
Selection

Default: 6
Min: 0
Max: 161

F5-06

Terminal P6-C6 Output
Selection

Default: 37
Min: 0
Max: 161

F5-07

Terminal M1-M2 Output
Selection

Default: F
Min: 0
Max: 161

F5-08

Terminal M3-M4 Output
Selection

Default: F
Min: 0
Max: 161

F5-09

DO-A3 Output Mode
Selection

0: Output terminals are each assigned separate output functions.
1: Binary code output
2: Use output terminal functions selected by parameters F5-01 through F5-08.

Default: 0
Min: 0
Max: 2

TOEP_C710616_38F_5_0.book 180 ページ 2013年12月4日 水曜日 午前9時56分