3 Electrical Installation
34
YASKAWA ELECTRIC TOEP C710616 38F YASKAWA AC Drive L1000A Quick Start Guide
◆ Main Circuit Wiring
This section describes the functions, specifications, and procedures required to safely and properly wire the main circuit
in the drive.
NOTICE: Only connect recommended devices to the drives braking transistor terminals. Failure to comply could result in damage to
the drive or braking circuit. Carefully review instruction manual TOBP C720600 0 when connecting a braking option to the drive.
NOTICE: Do not use the negative DC bus terminal “-” as a ground terminal. This terminal is at high DC voltage potential.
Improper wiring connections could damage the drive.
NOTICE: Equipment Hazard. Separate motor and/or braking circuit wiring (terminals, U/T1, V/T2, W/T3, +3, +2, +1,(-), B1, B2, from all
other wiring. Place motor wiring within its own conduit or cable tray with appropriate divider, and use shielded motor cable where
appropriate. Improper wiring practices could result in malfunction of drive due to electrical interference.
NOTICE: Equipment Hazard. Comply with proper wiring practices. The motor may run in reverse if the phase order is backward,
causing incorrect elevator direction movement. Connect motor input terminals U, V and W to drive output terminals U/T1,V/T2, and W/
T3. The phase order for the drive and motor should match.
NOTICE: Do not solder the ends of wire connections to the drive. Soldered wiring connections can loosen over time. Improper wiring
practices could result in drive malfunction due to loose terminal connections.
NOTICE: Do not switch the drive input to start or stop the motor. Frequently switching the drive on and off shortens the life of the DC
bus charge circuit and the DC bus capacitors, and can cause premature drive failures. For the full performance life, refrain from
switching the drive on and off more than once every 30 minutes.
■
Main Circuit Terminal Functions
Table 9 Main Circuit Terminal Functions
Note: Use terminal B1 and - terminals when installing the braking unit (CDBR type) to the drives with built-in braking transistor
(2A0008 to 2A0115, 4A0005 to 4A0060, and 5A0003 to 5A0041).
Terminal
Type
Function
Page
200 V
Class
Model
CIMR-
LU
2A0008 to 2A0075
2A0085, 2A0115
2A0145 to 2A0415
400 V
Class
4A0005 to 4A0039
4A0045, 4A0060
4A0075 to 4A0605
600 V
Class
5A0003 to 5A0027
5A0032, 5A0041
5A0052 to 5A0200
R/L1
Main circuit power supply input
Connects line power to the drive
S/L2
T/L3
U/T1
Drive output
Connects to the motor
V/T2
W/T3
B1
Braking resistor
Not available
Available for connecting a braking
resistor or a braking resistor unit option
–
B2
+2
• DC reactor connection
(+1, +2) (remove the
shorting bar between
+1 and +2)
• DC power supply
input (+1, –)
not available
For connection
• of the drive to a DC power supply
(terminals +1 and – are not UL
approved)
• of dynamic braking options
–
+1
• DC power supply
input (+1, –)
• DC power supply
input (+1, –)
• Braking unit
connection (+3, –)
–
+3
not available
For 200 V class: 100
Ω or less
For 400 V class: 10
Ω or less
For 600 V class: 10
Ω or less
Grounding terminal