beautypg.com

Yaskawa CIMR-LU Drives User Manual

Page 30

background image

3 Electrical Installation

30

YASKAWA ELECTRIC TOEP C710616 38F YASKAWA AC Drive L1000A Quick Start Guide

2.

Pull forward on the terminal cover to free it from the drive.

Figure 13

Figure 13 Removing the Terminal Cover

Reattaching the Terminal Cover
Models CIMR-LU2A0008 to 2A0075, 4A0005 to 4A0039, and 5A0003 to 5A0027

Power lines and signal wiring should pass through the opening provided.

Refer to Wiring the Main Circuit Terminal on

page 46

and

Wiring the Control Circuit Terminal on page 50

for details on wiring.

NOTICE: Equipment Hazard. Separate motor and/or braking circuit wiring (terminals, U/T1, V/T2, W/T3, +3, +2, +1,(-), B1, B2, from all

other wiring. Place motor wiring within its own conduit or cable tray with appropriate divider, and use shielded motor cable where

appropriate. Improper wiring practices could result in malfunction of drive due to electrical interference.

Reattach the terminal cover after completing the wiring to the drive and other devices.

Figure 14

Figure 14 Reattaching the Terminal Cover

Models CIMR- LU2A0085 to 2A0415, 4A0045 to 4A0605, and 5A0003 to 5A0027

After wiring the terminal board and other devices, double-check connections and reattach the terminal cover.

Refer to

Wiring the Main Circuit Terminal on page 46

and

Wiring the Control Circuit Terminal on page 50

for details on

wiring.

Figure 15

Figure 15 Reattaching the Terminal Cover

YEA_common

Connect ground wiring first,
followed by the main circuit,
and then wire the control circuit.
Power lines and signal wiring
exit through the opening provided.

YEA_common

Connect ground wiring first,
followed by the main circuit,
and then wire the control circuit.

YEA_common

TOEP_C710616_38F_5_0.book 30 ページ 2013年12月4日 水曜日 午前9時56分