Yaskawa iQpump1000 AC Drive Quick Start User Manual
Page 439

Register No.
Contents
00E2H
oFC1x Contents (CN5-C)
bit 0
Option RAM Fault (oFC10)
bit 1
Option Operation Mode Fault (SLMOD) (oFC11)
bit 2
Drive Receive CRC Error (oFC12)
bit 3
Drive Receive Frame Error (oFC13)
bit 4
Drive Receive Abort Error (oFC14)
bit 5
Option Receive CRC Error (oFC15)
bit 6
Option Receive Frame Error (oFC16)
bit 7
Option Receive Abort Error (oFC17)
bit 8 to F
Reserved
00E3H, 00E4H
Reserved
00E5H
oFC3x Contents (CN5-C)
bit 0
Comm. ID Error (oFC30)
bit 1
Model Code Error (oFC31)
bit 2
Sumcheck Error (oFC32)
bit 3
Comm. option timeout waiting for response (oFC33)
bit 4
MEMOBUS Timeout (oFC34)
bit 5
Drive timeout waiting for response (oFC35)
bit 6
CI Check Error (oFC36)
bit 7
Drive timeout waiting for response (oFC37)
bit 8
Control Command Selection Error (oFC38)
bit 9
Drive timeout waiting for response (oFC39)
bit A
Control Response Selection 1 Error (oFC40)
bit B
Drive timeout waiting for response (oFC41)
bit C
Control Response Selection 2 Error (oFC42)
bit D
Control Response Selection Error (oFC43)
bit E, F
Reserved
00E6H to 00FFH
Reserved
<1> Parameter o1-03, Digital Operator Display Selection, determines the units.
<2> Display is in the following units:
2A0004 to 2A0040, 4A0002 to 4A0023, and 5A0007 to 5A0017: 0.01 A units.
2A0056 to 2A0415, 4A0031 to 4A0675, and 5A0022 to 5A0242: 0.1 A units.
4A0930 and 4A1200: 1 A units.
<3> Communication error contents are saved until the fault is reset.
<4> Set the number of motor poles to parameter E2-04.
C.9 MEMOBUS/Modbus Data Table
YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide
439
C
MEMOBUS/Modbus Communications