U1 - 12, U1 - 19 – Yaskawa iQpump1000 AC Drive Quick Start User Manual
Page 402

No.
(Addr.
Hex)
Name
LCD Display
Description
Analog
Output Level
Unit
U1-12
(004B) Drive Status
Int Ctl Sts 1
Verifies the drive operation status.
U1 - 12=
00000000
During run
During zero-speed
During REV
During fault reset
signal input
During speed agree
Drive ready
During alarm
detection
During fault detection
1
1
1
1
1
1
1
1
No signal output
available
–
U1-13
(004E)
Terminal A1 Input
Level
Term A1 Level
Displays the signal level to analog input terminal A1.
10 V: 100%
0.1%
U1-14
(004F)
Terminal A2 Input
Level
Term A2 Level
Displays the signal level to analog input terminal A2.
10 V: 100%
0.1%
U1-15
(0050)
Terminal A3 Input
Level
Term A3 Level
Displays the signal level to analog input terminal A3.
10 V: 100%
0.1%
U1-16
(0053)
Output Frequency after
Soft Starter
SFS Output
Displays output frequency with ramp time and S-curves. Units
determined by o1-03.
10 V: Max
frequency
0.01 Hz
U1-18
(0061)
oPE Fault Parameter
OPE Error Code
Displays the parameter number that caused the oPE02 operation
error.
No signal output
available
–
U1-19
(0066)
MEMOBUS/Modbus
Error Code
Transmit Err
Displays the contents of a MEMOBUS/Modbus error.
U1 - 19=
00000000
CRC Error
Data Length Error
Not Used
Parity Error
Overrun Error
Framing Error
Timed Out
Not Used
1
1
0
1
1
1
1
0
No signal output
available
–
U1-24
(007D) Input Pulse Monitor
Term RP Inp Freq
Displays the frequency to pulse train input terminal RP.
Determined by
H6-02
1 Hz
U1-25
(004D)
Software Number
(Flash)
CPU 1 SW Number
FLASH ID
No signal output
available
–
U1-26
(005B) Software No. (ROM)
CPU 2 SW Number
ROM ID
No signal output
available
–
U1-29
(07AA) Software No. (PWM)
CPU 3 SW Number
PWM ID
Note:
This monitor is only displayed in models 4A0930
and 4A1200.
No signal output
available
–
U1-75
(0851)
Time-Hour/Minute
Time Hr Min HHMM Displays the current time (Hours and Minutes).
No signal output
available
–
U1-76
(0852)
Date – Year
Date Year
Displays the current year.
No signal output
available
–
U1-77
(0853)
Date – Month/Day
Date Mo Day MMDD Displays the current date (Month and Date).
No signal output
available
–
U1-78
(0854)
Date – Week Day
Date Week
Displays the current day of the week.
0: Sunday
1: Monday
2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
No signal output
available
–
U1-79
(0B9A)
<5>
PI Feedback Back-up
PI Fdbk Backup
Displays the PI Feedback Back-up signal (H3-oo = 24) used
when the primary PI Feedback (H3-oo = B) is lost.
No signal output
available
dep. on
P1-02
B.15 U: Monitors
402