8 control i/o connections – Yaskawa iQpump1000 AC Drive Quick Start User Manual

Page 151

background image

Output

4-20 mA

Outlet

Transducer

V+

AC

A2

EG

A2

AC
EG

iQpump 1

iQpump 2

+ -

External

24 Vdc Power Supply

Set Jumper S1 to the “I” Position (4-20 mA) for both iQpump drives (default).

V

I

A1 A2 A3

Jumper S1

Triplex System: Transducer Connection using Analog Input A2

A2 used for water level or suction pressure transducer.

Output

Set jumper S1 to the “I” position for the last iQpump drive on the network.
All other iQpump drives should have S1 set to the “V” position.

Last drive on network

4-20 mA

Transducer

V+

A2

AC
EG

AC

A2

EG

A2

AC

+V

EG

iQpump 1

iQpump 2

iQpump x

+ -

External

24 Vdc Power Supply

V

I

A1 A2 A3

Jumper S1

V

I

A1 A2 A3

Jumper S1

V

I

A1 A2 A3

Jumper S1

3.8 Control I/O Connections

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide

151

3

Electrical Installation